Save this Combination Table!
Please be sure to hand over this sheet to the user.
SAP-CMRV3146EH
<Combinations of Connectable Indoor Units>
The combinations of the indoor units listed in Table 1 on page 2 and Table 2 on page 3 are combinations solely of those units which can be operated concurrently. In addition to the combinations listed in the table, other combinations of indoor units are possible provided that the following conditions are satisfied.
Conditions:
1.At least two or more indoor units must be connected to the multi outdoor unit. It is not acceptable for only one indoor unit to be connected.
2.The total rated cooling capacity of the indoor units to be connected must be no more than 200% of the rated cooling capacity of the outdoor unit.
CAUTION
In this case, all the indoor units installed must not be operated concurrently under any circumstances. Otherwise, the air conditioner may not run properly and trouble may occur.
Example: When four indoor units are connected
If the following holds true
•Rated cooling capacity of
•Rated cooling capacity of indoor units: K1, K2, ... (kW)
Then:
C x 2 (200%) | K1 + K2 + |
8 x 2 2.2 + | 2.2 + 3.5 + 7.1 |
16 | 15 |
It is therefore possible to connect four units with respective capacities of 2.2 + 2.2 + 3.5 + 7.1. However, since this combina- tion is not found in the
NOTE
Be sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with only a single unit installed, the returning fluid to the compressor may cause a malfunction.