Contents
FILE NO
TECHNICAL & SERVICE MANUAL
DC INVERTER MULTI-SYSTEMAIR CONDITIONER
SAP-CMRV1926EH SAP-CMRV1426EHSAP-CMRV1936EH
Please Read Before Starting
WARNING When Wiring
When Transporting
When Installing
Table of Contents
SPECIFICATIONS
REFRIGERANT FLOW DIAGRAM
TROUBLESHOOTING
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
APPENDIX A
APPENDIX B
APPLICABLE INDOOR UNITS
1. OPERATING RANGE
2. SPECIFICATIONS
2-1.Unit Specifications
SAP-CMRV1426EH
SAP-KMRV96EH ⋅
SAP-CMRV1926EH
SAP-KMRV96EH ⋅ 1 + SAP-KRV186EH ⋅
SAP-CMRV1936EH
SAP-KMRV96EH ⋅
SAP-CMRV2446EH
SAP-KMRV96EH ⋅
SAP-CMRV3146EH
SAP-KMRV96EH ⋅
2-2-1.Outdoor Unit
2-2.Major Component Specifications
Outdoor Unit SAP-CMRV1426EH
Outdoor Unit SAP-CMRV1926EH
Outdoor Unit SAP-CMRV1936EH
Outdoor Unit SAP-CMRV2446EH
Outdoor Unit SAP-CMRV3146EH
2-3.Other Component Specifications
Resistance k ohm
Temperature C
Resistance k ohm
ID:18
3. DIMENSIONAL DATA
Outdoor Unit SAP-CMRV1426EH
Outdoor Unit SAP-CMRV1926EH
Unit mm
Outdoor Unit SAP-CMRV1936EH
Unit: mm 852-0-0010-10900-0
Outdoor Unit SAP-CMRV2446EH
Unit: mm 852-0-0010-11000-0
Outdoor Unit SAP-CMRV3146EH
Unit: mm 852-0-0010-11100-0
4. REFRIGERANT FLOW DIAGRAM
4-1.Refrigerant Flow Diagram
Outdoor Unit SAP-CMRV1426EH
Indoor unit
Indoor unit
Outdoor Unit SAP-CMRV1926EH
Outdoor unit
Indoor unit
Outdoor Unit SAP-CMRV1936EH
Outdoor unit
Indoor unit
Outdoor Unit SAP-CMRV2446EH
Outdoor unit
Insulation of Refrigerant Tubing
Outdoor Unit SAP-CMRV3146EH
Indoor unit
Outdoor unit
5. PERFORMANCE DATA
5-1.Temperature Charts
Outdoor Unit SAP-CMRV1426EH
Indoor Unit SAP-KMRV76EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1426EH
Indoor Unit SAP-KMRV96EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1426EH Indoor Unit
SAP-KMRV126EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1426EH
Indoor Unit SAP-KRV96EHDSA ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1426EH Indoor Unit
SAP-KRV126EHDS ⋅
Cooling Characteristics
Heating Characteristics
5-1-2.Temperature Charts SAP-CMRV1926EH
Outdoor Unit SAP-CMRV1926EH
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1926EH Indoor Unit
SAP-KMRV126EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1926EH Indoor Unit
SAP-KRV186EH ⋅
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1926EH Indoor Unit
SAP-KRV126EHDS ⋅
Cooling Characteristics
Heating Characteristics
5-1-3.Temperature Charts SAP-CMRV1936EH
Outdoor Unit SAP-CMRV1936EH Indoor Unit
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1936EH Indoor Unit
SAP-KMRV126EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1936EH
Indoor Unit SAP-KRV186EH ⋅
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV1936EH Indoor Unit
SAP-KRV126EHDS ⋅
Cooling Characteristics
Heating Characteristics
5-1-4.Temperature Charts SAP-CMRV2446EH
Outdoor Unit SAP-CMRV2446EH Indoor Unit
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV2446EH Indoor Unit
SAP-KMRV126EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV2446EH
Indoor Unit SAP-KRV186EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV2446EH
Indoor Unit SAP-KRV246EH ⋅
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV2446EH Indoor Unit
SAP-KRV126EHDS ⋅
Cooling Characteristics
Heating Characteristics
5-1-5.Temperature Charts SAP-CMRV3146EH
Outdoor Unit SAP-CMRV3146EH Indoor Unit
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV3146EH Indoor Unit
SAP-KMRV96EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV3146EH Indoor Unit
SAP-KMRV126EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV3146EH Indoor Unit
SAP-KRV186EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV3146EH Indoor Unit
SAP-KRV246EH ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV3146EH Indoor Unit
SAP-KRV96EHDSA ⋅
Cooling Characteristics
Heating Characteristics
Outdoor Unit SAP-CMRV3146EH Indoor Unit
SAP-KRV126EHDS ⋅
6-1.Electric Wiring Diagrams
6. ELECTRICAL DATA
and/or cleaning any electrical parts
Outdoor Unit SAP-CMRV1426EH
and/or cleaning any electrical parts
Outdoor Unit SAP-CMRV1926EH
and/or cleaning any electrical parts
Outdoor Unit SAP-CMRV1936EH
and/or cleaning any electrical parts
Outdoor Unit SAP-CMRV2446EH
and/or cleaning any electrical parts
Outdoor Unit SAP-CMRV3146EH
7. FUNCTIONS
7-1.Explanation of Functions
Clean defrost
Control/conditions
Unit operation
Explanation
Control/conditions
Unit operation
Explanation
COOL
1/f fluctuation fan
1/f fluctuation fan
Fig.
7-2.Protective Functions
2 Clean defrost
7-2-1.Defrost Detection and Release
1 Non-stopdefrosting
7-2-2.Current Control
Description of function
1Automatic frequency control
2 Current control
Reset conditions
7-2-3.Low Start Current
7-2-4.Compressor Temperature Control
7-2-5.Control at HEAT Start-up
8. TROUBLESHOOTING
8-2.Trouble Diagnosis by Error Monitor Lamps
8-2-1.Location of the Error Monitor Lamps
8-2-2.Display of the Error Monitor Lamps
the Power Lamp on the P.C.Board is turned off
8-3-1.Checking the outdoor unit
8-3.Checking the Outdoor System
8-3-2.Checking the defrost operation
8-4.Trouble Diagnosis of Each Part
8-4-1.Problems of Each Part and Inspection Points
1 Outdoor control circuit board
2 Fuse
3 Compressor
54-wayvalve
9 Breaker
8 Branch tubing temperature sensor
10 Refrigerant gas pressure
Diagnostic procedure
Diagnostic results
Remedy for symptom 3 to
Measurement location
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
9-1.Characteristics of New Refrigerant R410A
9-2.Checklist before Servicing
9.REFRIGERANT R410A
Tubing precautions
No addition of compressor oil for R410A
No use of refrigerant other than R410A
If refrigerant R410A is exposed to fire
9-4.Tubing Installation Procedures
9-3.Tools Specifically for R410A
For servicing, use the following tools for R410A
Tool Distinction
9-5.In Case of Compressor Malfunction
1 Recovering refrigerant
2 Replacing Compressor
3 Checking for sealing
Configuration and characteristics of cylinders
5 Recharging
Never charge a large amount
the unit. This may cause
9-6.In Case Refrigerant is Leaking
2 Recovering refrigerant
1 Detecting Leaks
3 Welding leaking points
9-7.Charging Additional Refrigerant
9-8. Retro-FittingExisting Systems
9-7-1.When Tubes are Extended
9-8-1.Use of Existing Units
APPENDIX A INSTALLATION INSTRUCTIONS
SAP-CMRV1426EH
INSTALLATION INSTRUCTIONS
For Outdoor Unit
7.CONNECTING A HOME AUTOMATION
INSTALLATION CHECK SHEET
English
In Case of Improper Installation
WARNING When Wiring
When Transporting
1-1.Tools Required for Installation not supplied
1-2.Accessories Supplied with Unit Table
English
1-3.Optional Copper Tubing Kit
English
2-1.Indoor Unit
AVOID
Fig.
2-2.Connecting Indoor Units
English
Table
Fig.
English
2-3.Outdoor Unit AVOID
Fig. 5a
Fig. 5b
English
2-5. Diagram of Outdoor Unit Installation
2-4.Outer Dimensions of Outdoor Unit
Never install only a single indoor unit
3-1. Embedding the Tubing and Wiring
3-4.Flaring Procedure with a Flare Tool
English
3-2. Drain Cap and Drain Elbow
3-5.Caution Before Connecting Tubes Tightly
English
Fig.
3-6.Tubing Connections
tubing and electric wiring
3-9.Finishing the Installation
English
Be sure to match refrigerant
English
4. Air Purging
Air Purging with a Vacuum Pump for Test Run
Fig.
English
Table
Be sure to completely insert
the hex wrench before
What is pump-down?
Pump-downprocedure
English
gas without releasing it into the atmosphere
5. Wiring Instructions
5-1.General Precautions on Wiring
5-2.Recommended Wire Length and Diameter
English
Each wire must be firmly connected
5-3.Wiring System Diagram
English
Fig.
5-4.How to Connect Wiring to the Terminal
Loose wiring may cause the
fore, be sure all wiring is
How to connect wiring to the terminal
5-5.Wiring Instructions for the Outdoor Unit
English
Be sure to perform grounding
Fig.
Checking tubing and wiring
English
6. Test Run
Performing a test run
7. Connecting a Home Automation Device
8. Installation Check Sheet
9. Electric Wiring Diagram
English
English
SAP-KMRV76/96/126EH
Fig. 33b
SAP-KRV96/126EHDS
SAP-CMRV1926EH SAP-CMRV1936EH SAP-CMRV2446EH
APPENDIX B INSTALLATION INSTRUCTIONS
SAP-CMRV3146EH
Español Français
Deutsch Italiano Português EÏÏËÓÈο
INSTALLATION INSTRUCTIONS
INSTALLATION SITE SELECTION
When Installing…
In Case of Improper Installation
WARNING When Wiring
When Transporting
1-1.Tools Required for Installation not supplied
1-2.Accessories Supplied with Unit Table
English
A B C D
English
2-1.Indoor Unit
AVOID
Fig.
2-2.Connecting Indoor Units
English
Table
Fig.
2 Connecting indoor unit for SAP-CMRV1936 A
3Connecting indoor unit for SAP-CMRV2446 A
English
Fig. 4b
English
Fig. 4e
Fig. 4f
Fig. 4g
4Connecting indoor unit for SAP-CMRV3146 A
English
Fig. 4h
Fig.
English
Fig. 4k
Fig. 4l
unit: mm
English
About
2-3.Outdoor Unit AVOID
Fig. 5a
2-4.Outer Dimensions of Outdoor Unit
Fig. 6c
Fig. 6d
unit: mm
2-5. Diagram of Outdoor Unit Installation
Never install only a single indoor unit
English
Fig. 6e
3-1. Embedding the Tubing and Wiring
3-4.Flaring Procedure with a Flare Tool
English
3-2. Drain Cap and Drain Elbow
D C B
3-5.Caution Before Connecting Tubes Tightly
English
inside surface is glossy and smooth
tubing and electric wiring
3-9.Finishing the Installation
English
Be sure to match refrigerant
Before using the vacuum pump
When using a hex wrench to open the spindle, an
This does not indicate a problem
English
English
Table
Be sure to completely insert
the hex wrench before
What is pump-down?
Pump-downprocedure
English
gas without releasing it into the atmosphere
5-1.General Precautions on Wiring
5-2.Recommended Wire Length and Diameter
English
Table
Each wire must be firmly connected
5-3.Wiring System Diagram
English
3 indoor units with SAP-CMRV1936
5-4.How to Connect Wiring to the Terminal
Loose wiring may cause the
fore, be sure all wiring is
How to connect wiring to the terminal
wiring. The units will not function if the wiring
Use a dedicated Air Conditioner circuit for power
English
Indoor unit A
Checking tubing and wiring
Access panel C
Performing a test run
Fig.
English
¢È¿ÁÚ·ÌÌ· ËÏÂÎÙÚÈ΋˜ ηψ‰›ˆÛ˘
SAP-KMRV74/94/124EH
Indoor Unit Unidad interior Appareil intérieur
SAP-KRV184/244EH
SAP-KMRV76/96/126EH
Fig. 33d
SAP-KRV96/126EHDS
English
Outdoor Unit Unidad exterior Appareil extérieur
Außengerät Unità Esterna Unidade exterior
∂͈ÙÂÚÈ΋ ÌÔÓ¿‰·
English
SAP-CMRV2446EH
Fig. 34c
SAP-CMRV3146EH
English
English
Español
Français
APPENDIX C UNIT COMBINATION TABLES
SAP-CMRV1426EH
2-RoomOutdoor Unit Combination Table
<Combinations of Connectable Indoor Units>
< Combinations of operatable indoor units >
SAP-CMRV1426EH
Rated cooling capacity: 4.0 kW
Table
2-RoomOutdoor Unit Combination Table
SAP-CMRV1926EH
<Combinations of Connectable Indoor Units>
SAP-CMRV1926EHV1924EH
Rated cooling capacity: 5.6 kW
Combinations of operatable indoor units
Table
SAP-CMRV1936EH
3-RoomOutdoor Unit Combination Table
<Combinations of Connectable Indoor Units>
SAP-CMRV1936EHRV1934EH
< Combinations of operatable indoor units >
Rated cooling capacity: 5.6 kW
Table
SAP-CMRV2446EH
4-RoomOutdoor Unit Combination Table
<Combinations of Connectable Indoor Units>
SAP-CMRV24446EH
Rated cooling capacity: 6.8 kW
< Combinations of operatable indoor units >
NOTENOTE
•When one or more SAP-KRVxxEHDSindoor units are operated concurrently with one or more SAP-KMRVxxEHindoor units, the performance specifications of the SAP-KRVxxEHDSmodels will decrease by 5% from those listed in the Table
4-RoomOutdoor Unit Combination Table
SAP-CMRV3146EH
Combinations of Connectable Indoor Units
< Combinations of operatable indoor units >
SAP-CMRV3146EH
Rated cooling capacity: 8.0 kW
2.65: SAP-KRV96EHDS 3.5: SAP-KRV126EHDS