Chapter 9: Message transfers

Set/reset relay (COM = 30(H))

[Format]

ËCommand

COM DSEG DADRL DADRH BLOC DATA

ËResponse

COM RSLT DSEG DADRL DADRH BLOC

COM

= 30(H)

 

DSED

= Segment (00 to 07, 10 to 2C(H))

See page 9-20.

DADRL, H

= Byte address (0000(H) to FFFF(H))

See page 9-20.

BLOC

= Bit position (00(H) to 07(H))

 

DATA

= Set/reset data (00(H): reset, 01(H): set)

[Function]

- Set/reset the relays shown in DSEG, DADR, and BLOC.

[Execution condition]

-Write enable mode : Mode 1 and mode 2

-PC operation status : Stopping, operating

[Example]

- Set relay number 07001.

 

Ë Command

 

 

 

 

 

 

 

 

 

 

 

Set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

00

 

C0

01

 

 

 

01

 

01

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

File 0

 

File address

 

 

 

 

Bit 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

000700(8) = 01C0(H)

 

 

 

 

 

 

 

Relay number 07001

ËResponse

30

00

00

 

C0

 

01

 

 

01

 

 

 

 

 

 

 

File address

 

 

 

 

Bit 1

 

 

 

 

 

 

 

 

 

 

 

File 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

000700(8)

= 01C0(H)

 

 

 

 

 

 

 

 

 

 

 

 

Relay number 07001

9-26