Chapter 12: Parameters

12-3 How to set parameters

[1] When the JW-20FL5/20FLT or Z-366J is used

Set parameters of JW-20FL5/20FLT and Z-336J as optional parameters of the control module (CPU board). Determine the area of the optional parameters using the module No. switch set value of JW- 20FL5/20FLT and Z-336J. The parameters occupy 64 bytes per module.

Module No. switch

Parameter address(H)

setting value

 

0

00 to 77

 

 

1

00 to 77

 

 

2

00 to 77

 

 

3

00 to 77

 

 

4

00 to 77

 

 

5

00 to 77

 

 

6

00 to 77

 

 

Note: Do not set switch SW3 outside the range of 0 to 6.

- Relationship between the host PC and the control module

FL-net module

Host PC

Control module

 

 

JW20H

JW-21CU/22CU

 

 

 

 

JW-20FL5

 

JW-31CUH1

 

 

JW-20FLT

JW30H

JW-32CUH1

 

 

 

 

 

 

 

JW-33CUH1/2/3

 

 

 

 

 

 

 

 

FL-net

Host J-board

CPU board

board

 

 

 

Z-336J

Z-300 series

Z-311J/312J/313J

 

 

 

Z-500 series

Z-511J

 

 

 

 

 

How to set the parameters using the JW-14PG

This paragraph describes parameter setting procedures (in system memory) using the hand-held programmer JW-14PG.

1Connect the JW-14PG to the PG port on the control module

(CPU board.)

 

2 Set the PC to program mode.

JW-14PG

 

3Set to the initial mode (parameter setting).

4Select the option parameter and enter "2" for the module No. switch number.

5Rewrite start switch to 00(H). Reading parameter address 77(8).

Reading a prameter address(H)

(The modules shown below are installation examples)

JW-20FL5

Control module (JW-33CUH)

Connection cable (JW-22KC/24KC)

JW-14PG screen

 

 

 

 

 

12

I

Parameter

 

 

 

0)

I/O

 

 

 

 

 

 

 

1)

Option

 

 

 

 

 

 

 

 

I

Parameter 0 - SW: 2

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

HEX

00

 

 

76

 

HEX

00

 

 

IParameter 0 - SW: 2

>77 HEX 00

6Enter IP address (192.168.250.3) for the parameter address 00 to 03(8). Decimal notation of parameter 00.

Decimal display of the setting of parameter 00

01

DCM

168

02

DCM

250

I Parameter

 

>03

DCM

003

 

 

 

Same as the above, enter the other parameter addresses.

12-3