Chapter 9: Message transfers

9-2 Transmission buffer

This section describes the transmission buffer that is used for sending and receiving data for the message transfer.

The transmission buffer area (+0000 to 4055(8)) is determined by entering top address to parameter (address 34 to 36(8)). (Parameter See Chapter 12.)

 

 

Transmission

Details

 

 

 

buffer address(8)

 

 

 

 

 

 

 

+0000

Receiving [data section]

 

 

 

 

 

 

 

to

- When writing 00(H) to address +4000, the received data will be

 

 

 

transferred to the control module (CPU board)

 

 

 

+1777

 

 

 

 

 

 

 

 

 

 

 

 

+2000

 

 

 

 

 

Sending [data section] *1

 

 

 

to

 

 

 

 

 

 

 

 

+3777

 

 

 

 

 

 

 

 

 

+4000

Node number of the node sending data.

 

 

 

 

 

 

 

 

+4001

Response message type (always 00(H))

 

 

 

 

 

 

 

 

+4002 to 4003

Transaction code (response).

 

 

 

 

 

 

 

 

+4004 to 4007

Top address of the virtual address space.

Receiving

 

 

 

 

 

 

 

Data length of response from the virtual

 

 

+4010 to 4011

[information section]

 

 

address space (word/byte).

 

 

 

 

 

 

 

 

 

 

 

+4012

Current fragment block number (always 01(H))

 

 

 

 

 

 

 

 

+4013

Total fragment block number (always 01(H))

 

 

 

 

 

 

 

 

+4014 to 4015

Current block length (byte)

 

9

 

 

 

 

 

 

 

+4016 to 4037

Reserved area

 

 

 

 

 

 

 

 

 

 

 

+4040

Node number of destination node. *2

 

 

 

 

 

 

 

 

+4041

Response message type (always 00(H))

 

 

 

 

 

 

 

 

+4042 to 4043

Transaction code (request).

 

 

 

 

 

 

 

 

+4044 to 4047

Top address of the virtual address space.

*1 Sending

 

 

 

 

 

 

 

Data length requesting to the virtual address

 

 

+4050 to 4051

[information section]

 

 

space (word/byte).

 

 

 

 

 

 

 

 

 

 

 

+4052

Current fragment block number (always 01(H))

 

 

 

 

 

 

 

 

+4053

Total fragment block number (always 01(H))

 

 

 

 

 

 

 

 

+4054 to 4055

Current block length (byte)

 

 

 

 

 

 

*1: The data in the transmission area [information section] and [data section] are transferred when 01(H) is written at the base address +301 in the communication control area. After sending data, JW-50FL clears the setting data of the sending data section.

*2: Enter 255(D) at the base address +4040. Then the data will be transferred to all the nodes currently connected.

9-4