Chapter 4: Name and Function of Each Part

4-4 JW-50FL

 

 

 

 

 

2

3

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

5

 

 

 

 

 

0

 

 

 

 

 

 

 

 

6

 

 

 

 

 

9

 

 

8 Switch SW3

 

 

 

8

7

 

 

 

 

 

 

 

 

 

SW3

 

 

 

 

 

 

 

 

 

 

4

(Factory setting: 0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7Switch SW3 (Factory setting: ON)

OFF ON

SW2

 

JW-50FL

1 LED indicator

LNK

S0

TX

S1

 

RX

S2

 

DC12V

S3

 

 

S4

 

TEST

S5

 

PER

S6

 

HER

S7

2 Connector for

P

programmer R

O

G

R

A

M

M

E

R

3 Connector for 10BASE5

10B5

4Connector for

10BASE-T

5 12 VDC power

10B-T

supply input terminal

12VIN

 

()

 

()

6 Reset switch

FG

RESET

 

Name

Function

 

Display panel

Displays the JW-50FL operating status using LEDs.

 

 

 

 

 

 

LNK

Lights at operating. Lights OFF at stopping.

 

 

 

 

 

 

TX

Blink at transmitting data.

 

 

 

 

 

 

RX

Blink at receiving data.

 

 

 

 

1

 

12 VDC

Lights when 12 VDC is supplied. (Only when 10BASE5 is used.)

 

 

 

 

 

 

TEST

Lights at test mode.

 

 

 

 

 

 

PER

Lights at parameter setting error.

 

 

 

 

 

 

HER

Lights at this module error.

 

 

 

 

 

S0 to S7 Indicates status of connection status monitor flag.

 

 

 

 

2Connector for programmer When using a remote monitor or remote programming function, connect a JW-14PG programmer.

3

Connector for 10BASE5

Connect the 10BASE5 transceiver cable.

Make sure to slide the lock securely to the "lock" position.

 

 

4Connector for 10BASE-T Connect 10BASE-T twisted-pair cable.

 

12 VDC power supply

When 10BASE5 is used, connect a commercially available DC power

5

supply that is designed to supply power to transceivers. The DC power

input terminal

 

supply must provide 12VDC 5% and 0.5 A or more.

 

 

 

 

 

 

 

6

Reset switch

Only used by SHARP engineers. Users should not press this switch.

 

 

 

 

 

 

ON

Turn ON when the shields on the 10BASE-T connectors or 10BASE5

 

 

connectors are connected to the FG (base) of the JW-50FL.

 

 

 

 

Switch SW2

 

 

7

 

Turn OFF when the shields on the 10BASE-T connectors or 10BASE5

 

 

OFF

connectors are not connected to the FG.

 

 

 

- Ground the FG line on the 12 VDC connector separately.

 

 

 

 

8

Switch SW3

Specify a parameter address (in system memory) from 0 to 4.

- See page 12-4.

 

 

 

Note: Only 10BASE5 or 10BASE-T protocol is used. Mixed use of these two types is not permitted.