Chapter 15: Appendix

[2] Wiring power lines and grounding equipment

This section describes how to wire power lines and ground lines in a distribution panel, or controller panel for the FL-net system.

When wiring power lines and making grounds, observe the precautions below.

1.Isolate the control power circuit from the controller power circuit using an isolation transformer with a static electricity protective function.

2.Ground the frames of the distribution panel and the control panel using class D grounding.

3.Provide an exclusive class D or better ground to the controller FG (frame ground) terminal. Do not connect this terminal to the controller frame.

4.The wiring for the power line to the controller should be as short as possible, using twisted power cables.

5.Connect the LG (line ground) terminal on the controller to the shield terminal on the isolation trans- former, and then to the frame ground on the panel.

Control

Distribution

Operation

Control panel

power

panel

preparation

 

 

 

Relay circuit

 

PLC, etc.

 

Panel

Panel ground

Controller ground

Class

ground

(5.5 mm2 or larger)

(5.5 mm2 or larger)

 

Class

Class

D ground

D ground

D ground

An example of how to ground the FL-net system