Pump Settings Menu

The Pump Settings menu lets you set all pump parameters. These include:

Pump Mode

Blowback

Delay Time

Setting the Pump Mode

The first setting to be configured is the Pump mode. This function tells the controller how many pumps are connected to the system and how the pumps are to be controlled.

You can select two pump modes: Single Pump mode and Dual Pump mode. In Single Pump mode (default), one (1) pump is used to convey material to all 12 stations. In Dual Pump mode, two (2) pumps are used simultaneously, resulting in a more efficient conveying process.

From the main operating display (OFFLINE):

1. Press the MENU key repeatedly until the screen displays the following:

PUMP SETTINGS?

NO/YES

To enter the Pump Settings menu:

1.Press the YES key.

2.Press the NO or MENU key repeatedly until the screen displays the following:

PUMP MODE?

NO/YES

To enter the Pump Mode setting menu: 1. Press the YES key.

The screen displays the following:

SET PUMP MODE?

Y=SINGLE N=DUAL

2–Pump 12-Station Controllers

Chapter 3: Installation

27

Page 28
Image 28
Sterling 882.00249.00 manual Pump SETTINGS? NO/YES, Pump MODE? NO/YES, SET Pump MODE? =SINGLE N=DUAL, Pump Settings Menu