Sterling 882.00249.00 Service Only Information, SET Ramp UP TIME? NO/YES, Service Settings Menu

Models: 882.00249.00

1 70
Download 70 pages 6.71 Kb
Page 58
Image 58

Chapter 8: Service Only Information

Note: Hidden, programmable features and hidden menu pages should not be made available to floor operators. These pages include the Service Information located in this section. Unauthorized changes to these factory settings by inexperienced operators may prevent the controller from operating properly, and may void part or all of the warranty.

Note: If this manual is to be used on the floor by the operator, keep this section separate from the rest.

8-1 Service Settings Menu

Setting the Ramp Up Time

Ramp up time is a delay that allows the pump to establish full speed before the valve opens. This delay defaults to 1.5 seconds and should not be altered unless instructed to do so by the Service Department.

SET RAMP UP TIME?

NO/YES

At the above message prompt:

Press the YES key to enter the Ramp Up Time menu.

SELECT PUMP 1 OR 2

USE KEYPAD TO ENTER

Select the pump for altering ramp up time.

RAMP UP DLY: 1.500s

SETTING FOR PUMP n

Using the keypad:

Enter the new time and press the ENTER key to save the new setting.

2–Pump 12-Station Controllers

Chapter 8: Service Only Information

57

Page 58
Image 58
Sterling 882.00249.00 manual Service Only Information, SET Ramp UP TIME? NO/YES, Ramp UP DLY 1.500s Setting for Pump n