Connecting Power Cables

Caution – The Netra 1290 server is designed to work with power systems having a grounded neutral conductor. Do not connect the equipment into any other type of power system. Contact your facilities manager or a qualified electrician to determine what type of power is supplied to your building.

Caution – The Netra 1290 server is shipped with grounding-type (three-wire) power cords. Always connect the cords into grounded power outlets.

Caution – The socket outlets must be installed near the equipment and easily accessible.

To Connect the Power Cables

1.Turn the system power switch to the Standby position.

Caution – The On/Standby power switch does not isolate the equipment. The power cords are the primary means of disconnection for this product.

2.Turn the cabinet power off if you are using a powered cabinet. Refer to the installation guide that came with the cabinet.

3.Label both ends of the 4 power cords.

Label two power cords Source A and label the other two power cords Source B.

4.Connect the power cables to the server.

a.Connect the Source A power cords to AC0/DC0 and AC1/DC1 on the server and the Source B power cords to AC2/DC2 and AC3/DC3 on the server.

b.Run the power cords through the CMA and secure them with tie wraps. Ensure that the CMA can extend and retract without dislodging the power cords.

5.Connect the server to the power source.

Chapter 1 Unpacking and Installing the Server 33

Page 45
Image 45
Sun Microsystems 1290 manual Connecting Power Cables, To Connect the Power Cables