3. Insert the pins in the front bracket into cabinet holes 22 and 33 (FIGURE 1-6).

Front bracket

 

secured to outer cabinet holes

Adjustable bracket

 

 

secured to inner cabinet holes

FIGURE 1-6Installing the Slide Rails in a Sun Fire Cabinet

The pins hold the bracket in place until the bracket is secured.

4.Secure the adjustable bracket into cabinet holes 24 and 31 with two No. 10-32 UNF screws.

5.Secure the front bracket into cabinet holes 24 and 31 with two No. 10-32 UNF screws.

6.Repeat Step 1 through Step 5 for the second slide rail assembly.

Note – Mounting the server in cabinet holes 24 and 31 allows for 10-inches of space beneath the server in order to service the backplane.

To Install the Slide Rail Assemblies in the Top Position

1.Adjust the position of the adjustable bracket on each slide rail assembly.

a.Loosen the two nuts that secure the adjustable bracket.

b.Reposition the adjustable bracket to the location stamped “SUNFIRE” on the rear bracket and secure the adjustable bracket.

2.Adjust the length of each slide rail assembly.

10 Netra 1290 Server Installation Guide • May 2006

Page 22
Image 22
Sun Microsystems 1290 manual To Install the Slide Rail Assemblies in the Top Position