10.7.5 Control and monitoring signals connector
9 | CS | Current sharing signal. When |
|
| of the units should be connected to allow current balance between units. |
|
|
|
10 | V_TRIM_C | Connection for output voltage trimming of FPS1000 unit "C". The voltage can be |
|
| trimmed within its range specifications. |
|
|
|
11 | SIGNAL_RETURN | Return for the following control and supervisory signals: On/Off, DC_OK, |
|
| Over_temperature Alarm, AC_Fail, Auxiliary 12V supply. The Signal return is isolated |
|
| from the output terminals. |
|
|
|
12 | DC_OK_C | Open collector signal, referenced to pin 11 (Signal Return). On when the output voltage |
|
| of FPS1000 unit "C” is higher than ≥ |
|
| and the maximum external voltage is 15V. |
|
|
|
13 | +SENSE | Positive sensing. The +Sense signal should be connected to the positive terminal of |
|
| the load. The +Sense and |
|
| up effect. The maximum load wires drop compensation is 1V/wire. |
|
|
|
14 | AC_FAIL_B | Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage |
|
| of FPS1000 unit "B" is ≥85Vrms. The maximum sink current is 10mA, and the maximum |
|
| external voltage is 15Vdc. |
|
|
|
15 | ON/OFF_B | Turns the output of FPS1000 unit "B" to On and Off by electrical signal or dry contact |
|
| between pin 15 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open: |
|
| Off. The maximum source current is 2.6mA. |
|
|
|
16 | AC_FAIL_A | Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage |
|
| of FPS1000 unit "A" is ≥85Vrms. The maximum sink current is 10mA, and the maximum |
|
| external voltage is 15Vdc. |
|
|
|
17 | NC | Not connected |
18 | NC | Not connected |
|
|
|
19 | NC | Not connected |
|
|
|
20 | SCL (I2C) | Serial Clock used in the I2C interface option. Refer to the I2C interface description in |
|
| the Chapter 7 in this Instruction Manual. |
|
|
|
21 | SDA (I2C) | Serial Data used in the I2C interface option. Refer to the I2C interface description in |
|
| the Chapter 7 in this Instruction Manual. |
|
|
|
22 |
| Negative sensing. The |
|
| of the load. The |
|
| |
|
|
|
23 | TEMP_ALARM_C | Open collector signal, referenced to pin 11 (Signal Return). On when the internal temperature |
|
| of FPS1000 unit "C" is within safe limit, Off approx 10°C below Thermal shut down. The |
|
| maximum sink current is 10mA and the maximum external voltage is 15V. |
|
|
|
24 | AC_FAIL_C | Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage |
|
| of FPS1000 unit "C" is ≥85Vrms. The maximum sink current is 10mA, and the maximum |
|
| external voltage is 15Vdc. |
|
|
|
25 | ON/OFF_C | Turns the output of FPS1000 unit "C" to On and Off by electrical signal or dry contact |
|
| between pin 25 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open: Off. |
|
| The maximum source current is 2.6mA. |
|
|
|
28