3.7.7 Input/Output connector information
The FPS1000 series uses male connector PCIB24W9M400A1, Positronic connector. To mate FPS1000 series to the load circuitry, use female connector
Pin No | Function | Description |
1,2,4 | +V | Positive output voltage. Maximum current capacity: 24A/contact. |
3,5,6 | Negative output voltage. Maximum current capacity: 24A/contact. | |
7 | On/Off control | Turns the output to On and Off by electrical signal or dry contact between pin 7 |
|
| and pin 10 (Signal Return). 0~0.6V or Short: On, 2~15V or Open: Off. |
|
| The maximum source current is 2.6mA. |
8 | +Sense | Positive sensing. The +Sense signal should be connected to the positive terminal |
|
| of the load. The +Sense and |
|
| |
|
|
|
9 | DC_OK | Open collector signal, referenced to pin 10 (Signal Return). On when Vout≥80%+/- |
|
| 5% of its rated value. The maximum sink current is 10mA and the maximum |
|
| external voltage is 15V. |
10 | Signal_Return | Return for the following control and supervisory signals: On/Off, DC_OK, |
|
| Over_temperature Alarm, AC_Fail, Auxiliary 12V supply. The Signal return is isolated |
|
| from the output terminals. |
11 | AC_Fail | Open collector signal, referenced to pin 10 (Signal Return). On when the input |
|
| voltage is ≥85Vrms. The maximum sink current is 10mA and the maximum external |
|
| voltage is15Vdc. |
12 | Over | Open collector signal, referenced to pin 10 (Signal Return). On when the internal |
| Temperature | temperature is within safe limit, Off approx. 10°C below Thermal shut down. The |
| Alarm | maximum sink current is 10mA and the maximum external voltage is 15V. |
|
|
|
13 | Negative sensing. The | |
|
| |
|
| the load. The |
|
| effect. The maximum load wires drop compensation is 1V/wire. |
|
|
|
14 | V_Trim | Connection for output voltage trimming. The voltage can be trimmed within its |
|
| |
|
| range specifications. |
|
|
|
15 | CS | Current sharing signal. When units are connected in parallel, the CS pins of the |
|
| units should be connected to allow current balance between units. |
16 | +12V Auxiliary | Auxiliary voltage output, 11.2~12.5V, referenced to pin 10 (Signal Return). The |
|
| maximum load current is 0.25A. This output has built in Oring diode and is not |
|
| controlled by the On/Off control. |
|
|
|
17 | SDA | Serial Data used in the I2C interface option. Refer to the I2C interface description. |
18 | SCL | Serial Clock used in the I2C interface option. Refer to the I2C interface description. |
19,20,21 | A0, A1, A2 | I2C interface address lines. Refer to the I2C interface description in Chapter 7. |
22 | ACG | AC Ground connection, refer to the safety instructions for safety standards requirements. |
|
| For "/P" models the AC Ground is connected via the front panel IEC inlet. |
23 | AC Line | AC Line connection, refer to the safety instructions for safety standards requirements. |
|
| For "/P" models the AC Line is connected via the front panel IEC inlet. |
24 | AC Neutral | AC Neutral connection, refer to the safety instructions for safety standards requirements. |
|
| For "/P" models the AC Neutral is connected via the front panel IEC inlet. |
Table
3.7.8 REPACKAGING FOR SHIPMENT
The original packaging material is reusable. If the original package is not available, contact the Lambda Sales or service facility near you for details on obtaining suitable packaging and shipping information. To ensure safe transportation of the instrument, it is recommended to use the original package.
Please attach a tag to the power supply describing the problem and specifying the owner, model number and serial number of the power supply.
10