TOA Electronics FPS-T1U FPS-S1U Instruction Manual, Chapter, FPS-S1U RACK SPECIFICATIONS

Models: FPS1000-48 FPS-T1U FPS-S1U FPS1000-32 FPS1000-12 FPS1000-24

1 57
Download 57 pages 10.2 Kb
Page 28
Image 28
FPS-S1U Instruction Manual

 

 

 

 

 

 

FPS-S1U Instruction Manual

CHAPTER 9

FPS-S1U RACK SPECIFICATIONS

1

 

Number of power supply modules

(*1)

---

Maximum 3 x FPS1000 modules of the same output voltage rating.

2

 

Maximum output power

(*2)

W

3000

3

 

Input voltage / frequency range

(*3)

---

85~265Vac continuous, 47~63Hz, Single phase

4

 

Maximum input current (at 100/200Vac)

A

12.0/6.0 for each FPS1000 unit installed

5

 

AC input connector

 

---

FPS-S1U :IEC inlet for each power supply module . FPS-S1U/P :None

6

 

Output terminals

 

---

Bus-bars.Refer to outline drawing.

7

 

Remote sensing

 

(*4)

V

Possible.

8

 

Parallel operation

 

---

Possible. Up to 3 racks with max 8 FPS 1000 units of the same voltage and current rating.

9

 

Series operation

 

(*5)

---

Possible. Up to 2 racks of the same voltage and current rating

 

 

 

 

 

 

Separate control for each FPS 1000 unit , By electrical signal or dry contact

10

Remote On/Off control

 

---

ON: 0~0.6V or short. OFF: 2~15V or open.

 

 

 

 

 

 

Separate control for each FPS1000 unit, Open collector signal.

11

DC_OK signal

 

 

---

On when Vout >80% +/-5%. Max.sink current: 10mA

 

 

 

 

 

 

Separate control for each FPS1000 unit ,Open collector signal.

12

AC fail signal

 

 

---

Refer to Instruction Manual

 

 

 

 

 

 

Separate control for each FPS1000 unit ,Open collector signal.

13

Over Temperature alarm signal

 

---

Refer to Instruction Manual

14

Vout voltage trimming

 

---

Possible, via separate control for each FPS1000 unit .Refer to Instruction Manual.

15

Auxiliary power supply

 

---

11.2~12.5VDC.Maximum output current:0.25A*Number of installed FPS1000 units.

16

Operating temperature

 

---

0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C.

17

Storage temperature

 

---

-30~85°C

18

Operating humidity

 

---

10~90% RH, no condensation.

19

Storage humidity

 

---

10~90% RH, no condensation.

20

Vibration

 

 

---

Built to meet ETS 300 019

21

Shock

 

 

---

Built to meet ETS 300 019

22

Applicable safety standards

 

---

UL60950-1, EN60950-1

 

 

 

 

 

 

Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground:

23

Withstand voltage

 

---

500Vrms, 1min.

24

Insulation resistance

 

---

More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc

25

Weight (Typ)

 

 

Kg

3.7

26

Size (W*H*D)

 

 

---

440x44x351mm. Refer to Outline Drawing.

27

Warranty

 

 

Yr

Two Years

Notes:

 

 

 

 

*1:

The Output of all the FPS1000 modules are connected in parallel in the rack.

*2:

For input voltage lower than 100Vac, maximum output power derated by 10% of the power rating.

*3:

For cases where conformance to to various safety standards (UL, EN etc.) is required, to be described

 

 

as 100-240Vac (50/60Hz).

 

 

 

*4:

Remote sensing can compensate up to 1V drop on each load wire.

*5:

Not apllicable for units with I2C bus option.

25

Page 28
Image 28
TOA Electronics FPS-T1U, FPS1000-24, FPS1000-12, FPS1000-32 FPS-S1U Instruction Manual, Chapter, FPS-S1U RACK SPECIFICATIONS