U-Line 2275DWRWOL Échelon Service Menu, Service and Repair, 3-32, Forced Defrost, Relay Status

Models: 2175R 2115R 2115WC 2175/2275DWRR 2115WCOL 2175BEV 2175WC 2175RF CLR2160 CO2175/CO2275DWR CO2175F CLRCO2175 2275DWRWOL 2175WCOL 2275DWRWS

1 180
Download 180 pages 38.87 Kb
Page 47
Image 47
FORCED DEFROST

Section 3 - Service and Repair

FORCED DEFROST

This will allow the unit to defrost quickly. For R and WC units, this is just an off cycle. For units with hot gas defrost the unit will enter a hot gas defrost per the specification. Hold the LIGHT key and press ON/OFF three times. The unit will beep once when entering this mode. To exit this mode either do the same key combination or turn the unit off via the display. Not available on CLR2160.

ICE THICKNESS ADJUST

This will allow addition or subtraction of up to five minutes from the ice-making cycle. To enter this mode hold the up arrow and press the down arrow three times. The unit will beep once and display the current ice thickness. To adjust up or down use the arrows. Press LIGHT key when completed. Please refer to the ice thickness section of the manual to view proper cube sizes and recommendations.

Only available on CLR2160 and CLRCO2175.

TEMPORARY SHUTDOWN/OFFICE MODE

In some cases it may be requested for the unit to be shut down for short periods during meetings for example. To do this hold the down arrow and press the up arrow three times. The unit will beep once and show OFF on the display. This mode can be canceled by removing power from the unit or turning it on via the display. The mode will automatically be changed back to ON after three hours.

Only available on CLR2160 and CLRCO2175.

RELAY STATUS

To see which relays are operating, hold the down arrow and hit ON/ OFF three times. The unit will scroll through all relays and whether they are on or off. See specific unit section for explanation.

MODEL NUMBER CHANGE

Only the main circuit board requires model number selection. The display board is universal and will automatically adapt to the unit it is plugged into. The model number can be changed with the board installed or uninstalled from the unit. To program uninstalled you will need a display board and a power supply. For the power supply hook a neutral wire up to pin 10 and a 120V wire to pin 8 of the circuit board.

1.Plug in unit.

2.The display may show a SP or --, either is OK.

3.Install a jumper on J3. The jumper can be obtained from U-Line P/ N 68080.

4.Hold down WARMER, COLDER and LIGHT buttons until display shows model number and main board beeps.

5.Use WARMER/COLDER to select new model number.

61-2175R 120V

75-2175R 220V

62-2175WC 120V

76-2175WC 220V

63-2175BEV 120V

77-2175BEV 220V

64-CO2175F 120V

78-CO2175 220V

65-2175RF 120V

79-2175RF 220V

66-CO2175DWR 120V

80-CO2175DWR 220V

67-CLR2160 120V

81-CLR2160 220V

68-CLRCO2175 120V

82-CLRCO2175 220V

70-2175DWR 120V

85-2275DWRWS 120V

71-2115R 120V

86-2275DWRWS 220V

72-2115WC 120V

87-2275ZWC 120V

73-2115R 220V

88-2275ZWC 220V

74-2115WC 220V

 

6.Press and release LIGHT key.

7.Wait for display to stop flashing.

8.Remove jumper from board.

9.Unplug unit and wait five seconds.

10.Plug unit back in.

Échelon Service Menu

Enter service menu by holding up arrow and pressing LIGHT three times. Select option 1 to 27 with the up and down arrows. To enter the option, press the LIGHT key. If changing a setting, you must press the LIGHT key again to retain the changed setting.

When entering service mode all other modes are cancelled and the unit will stop operating. When exiting service mode the unit will begin to operate normally, however the four-minute compressor off cycle still applies.

1.Light all LED segments.

This will illuminate all the LEDs on the board to ensure they work properly.

2.Thermistor 1 status—Temperature, E1, or E2.

This will show the pure thermistor reading with no offsets taken into account. When placed in ice water this thermistor should read 32°F in this menu option. Not available on CLR2160.

3.Error log

A list of the errors in the order they occurred will scroll once on the display. Repeat if desired. Once viewed perform option 12 to clear the errors from memory.

4.Defrost information

Displays the number of defrosts that have occurred in the past 24 hours.

5.Compressor runtime based on last cycle

This will show the number of minutes the compressor has run in the prior cycle (or current cycle if the compressor was running when service mode was entered).

6.Defrost length adjustment—up to 99 minutes

The length of the defrost can be adjusted up to 99 minutes long. The other defrost parameters still apply. Lengthening a defrost may cause higher than normal temperatures in the refrigerator section. Not available on CLR2160.

7.Light switch 1 status—0 or 1

This will tell if the light should turn off with the door switch or not. At the “0” reading the light should be off with the door closed and on with the door open. At the “1” reading the light stays on always.

8.Display toggle status—0 or 1

This will tell if the display should turn off with the door switch or not. At the “0” reading the display should be off with the door closed and on with the door open. At the “1” reading the display stays on always.

9.Restore factory defaults

This will restore the default set-point, defrost and offset values.

10.Adjust thermistor 1 offset—10 to +10F

3-32

Page 47
Image 47
U-Line 2275DWRWOL Échelon Service Menu, Service and Repair, 3-32, Forced Defrost, Ice Thickness Adjust, Relay Status