Briggs & Stratton PRO4000 01932 Using the Generator, Operating Generator, System Ground

Page 6

BSPP Generator

USING THE GENERATOR

System Ground

The generator has a system ground that connects the generator frame components to the ground terminals on the AC output receptacles.The system ground is connected to the AC neutral wire (the neutral is bonded to the generator frame).

Special Requirements

There may be Federal or State Occupational Safety and Health Administration (OSHA) regulations, local codes, or ordinances that apply to the intended use of the generator. Please consult a qualified electrician, electrical inspector, or the local agency having jurisdiction.

In some areas, generators are required to be registered with local utility companies.

If the generator is used at a construction site, there may be additional regulations which must be observed.

Connecting to a Building’s Electrical System

Connections for standby power to a building’s electrical system must be made by a qualified electrician.The connection must isolate the generator power from utility power, and must comply with all applicable laws and electrical codes.

DANGER

Generator produces powerful voltage.

Failure to isolate generator from power utility can result in death or injury to electric utility workers due to backfeed of electrical energy.

When using generator for backup power, notify utility company. Use approved transfer equipment to isolate generator from electric utility.

Use a ground fault circuit interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.

DO NOT touch bare wires or receptacles.

DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.

DO NOT operate generator in the rain.

DO NOT handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.

DO NOT allow unqualified persons or children to operate or service generator.

OPERATING THE

GENERATOR

CAUTION

Exceeding generators wattage/amperage capacity can damage generator and/or electrical devices connected to it.

See “Don’t Overload Generator” on page 12.

Start generator and let engine stabilize before connecting electrical loads.

Connect electrical loads in OFF position, then turn ON for operation.

Turn electrical loads OFF and disconnect from generator before stopping generator.

IMPORTANT: If equipped, always unplug the battery float charger before starting the generator.

Starting the Engine

Disconnect all electrical loads from the generator. Use the following start instruction steps in numerical order:

1.Make sure unit is on a level surface.

IMPORTANT: Failure to start and operate unit on a level surface will cause the unit not to start or shut down during operation.

2.Turn fuel valve to “On” position (Figure 1).

Figure 1 — Fuel Shut-off Valve

3.Make sure Idle Control switch is in “Off” position (Figure 2).

Figure 2 — Idle Control Switch

6

Image 6
Contents PRO4000 01932 PRO6500 01933 Table of Contents Safety RulesEquipment Description When Transporting or Repairing Equipment When Adding FuelWhen Operating Equipment When Storing Fuel or Equipment with Fuel in TankWhen Adjusting or Making Repairs to Your Generator Unintentional sparking can result in fire or electric shockRemove Generator From Carton AssemblyBefore Starting the Engine Add Engine Oil and FuelOperating Generator Using the GeneratorConnecting to a Building’s Electrical System System GroundStopping the Engine Connecting Electrical LoadsCharging a Battery Operating Automatic Idle ControlCold Weather Operation WindReceptacles 120/240 Volt AC, 30 Amp, Locking Receptacle120/240 Volt AC, 20 Amp Locking Receptacle Volt AC, 30 Amp Locking Receptacle Volt AC, 20 Amp, Duplex ReceptacleVolt DC, 10 Amp Receptacle Test your Gfci circuit breaker every month, as follows Ground Fault ProtectionTest Gfci Circuit Breaker During Generator UseCapacity Power ManagementDont Overload Generator ExampleFuel Valve Maintenance General Maintenance RecommendationsEngine Maintenance Generator MaintenanceGenerator Storage Generator CleaningStorage Engine StorageBspp Generator Troubleshooting Problem Cause CorrectionOUR Equipment Description DE L Équipement Symboles de Danger et MoyensTable DES Matières Règles DE SécuritéLorsque Léquipement Fonctionne Le générateur produit une tension élevéeLorsque Vous Ajoutez DU Carburant Lorsque Vous Transportez OU Réparez LéquipementUnintentional peut résulter dans feu ou électrique Lorsque Vous Réglez OU Réparez Votre GénérateurAjouter de lhuile à moteur et du combustible AssemblageAvant LE Démarrage DU Moteur Enlever le générateur de la boiteMise à la terre du système Utilisation DE LA GénératriceUtilisation DU Générateur Branchement au système électrique dun édificeFonctionnement du Contrôle Automatique du Ralenti Branchement des Charges ÉlectriquesArrêt du Moteur Recharge d’une BatterieExploitation PAR Temps Froid Fil noirPrise à Verrouillage de 120/240 Volts c.a., 20 Ampères Prises DE CourantPrise à Verrouillage de 120/240 Volts c.a., 30 Ampères Rallonge a 4 fils 240V 120V Neutre PositifPrise de 10 Ampères, 12 Volts c.c Prise à Verrouillage de 120 Volts c.a., 30 AmpèresVolts c.a., 20 Ampères Prise de Courant Double Rallonge a trois cablesProtection contre les fuites de terre Mise à lessai du disjoncteur GfciPendant le fonctionnement de la génératrice Gestion de la Consommation NE PAS Surcharger GénérateurCapacité ExempleEntretien du Générateur Recommandations Générales D’ENTRETIENEntretien du Moteur Entretien de la Vanne de CombustibleRemisage du Générateur RemisageNettoyage de Générateur Remisage du MoteurRemarques Dépannage Notre Équpement Advertencia Tabla DE ContenidosDescripción DEL Equipo Instrucciones DE SeguridadCuando Añada Combustible PeligroLos generadores producen un voltaje muy poderoso Cuando Opere EL EquipoPrecaución Cuando Ajuste O Haga Reparaciones a SU GeneradorQuemaduras severas pueden ocurrir al hacer contacto Para Retirar el Generador de la Caja MontajeAntes DE Darle Arranque AL Motor Agregar Aceite al Motor y GasolinaTierra del Sistema USO DEL GeneradorOperando EL Generador Precaución Conexión al Sistema Eléctrico de un EdificioParado Del Motor Carga de la BateriaConexion De Cargas Electricas Funcionamiento del Control Automático de Marcha en VacíoOperación Durante UN Clima Frío Figura 27 Conexiones de la BateríaReceptáculos 120/240 Voltios AC, 30 Amp, Receptáculo de Seguridad120/240 Voltios AC, 20 Amperios, Receptáculo de Seguridad Tomacorrientes de 120 Voltios AC, 30 Amperios Tomacorrientes de 12 Voltios DCVolt AC, 20 Amperios, Receptáculos Dobles Protección Contra Fallos de Conexión a Tierra Compruebe el Disyuntor GfciMientras se Utiliza el Generador Control de la Energía No Sobrecargue GeneradorCapacidad EjemploMantenimiento del Generador Recomendaciones Generales DE MantenimientoMantenimiento del Motor Mantenimiento de la Válvula de CombustibleAlmacenando el Generador AlmacenamientoPara Limpiar el Generador Almacenando el MotorProblemo Accion Causa Diagnositicos DE AveríasGarantía Limitada