NOTE: Use an automotive hydrometer to test battery state of charge and condition. Follow the hydrometer manufacturer’s instructions carefully. Generally, a battery is considered to be at 100% state of charge when specific gravity of its fluid (as measured by hydrometer) is 1.260 or higher.

Cold Weather Operation

Under certain weather conditions (temperatures below 40°F [4°C] combined with high humidity), your generator may experience icing of the carburetor and/or the crankcase breather system. To reduce this problem, you need to perform the following:

1.Make sure generator has clean, fresh fuel.

2.Open fuel valve (turn valve to open position).

3.Use SAE 5W-30 oil.

4.Check oil level daily or after every eight (8) hours of operation.

5.Maintain generator following Maintenance Schedule in Maintenance section.

6.Shelter unit from elements.

Creating a Temporary Cold Weather Shelter

1.For temporary shelter, the original shipping carton can be used.

2.Cut off top carton flaps and one long side of carton to expose muffler side of unit. If required, tape up other sides of carton to fit over generator as shown.

Wind

Typical Generator

Shown

NOTE: If required, remove wheel kit to fit carton over generator as shown.

3.Cut appropriate slots to access receptacles of unit.

4.Face exposed end away from wind and elements.

5.Locate generator as described in the section Generator Location. Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.

WARNING Running engine gives off carbon

monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures,

nausea, fainting or death.

Operate generator ONLY outdoors.

Install a battery operated carbon monoxide alarm near the bedrooms.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes, or other openings.

DO NOT start or run engine indoors or in an enclosed area, (even if windows and doors are open), including the generator compartment of a recreational vehicle (RV).

6.Start generator as described in the section Starting the Engine, then place carton over generator. Keep at least 5 ft. (1.5 m) clearance on all sides of generator including overhead with shelter in place.

WARNING Contact with muffler area can result in serious burns.

Exhaust heat/gases can ignite combustibles, structures or damage

fuel tank causing a fire.

DO NOT touch hot parts and AVOID hot exhaust gases.

Allow equipment to cool before touching.

Keep at least 5 feet (152 cm) of clearance on all sides of generator including overhead.

Remove shelter when temperatures are above 40°F [4°C].

7.Remove shelter when temperatures are above 40°F [4°C].

8.Turn engine OFF and let cool two (2) minutes before refueling. Let any spilled fuel evaporate before starting engine.

Building a Cold Weather Shelter

1.Using non combustible material with a fire rating of at least one hour, build a shelter that will enclose three sides and the top of the generator. Make sure muffler side of generator is exposed.

NOTE: Contact your local building material supplier for non combustible materials with a fire rating of at least one hour.

IMPORTANT: Be sure shelter can easily be repositioned for change in wind direction.

2.DO NOT enclose generator any more than shown. Shelter should hold enough heat created by the generator to prevent icing problem.

NOTE: If a wheel kit is installed on the generator, enlarge shelter accordingly.

3.Follow steps 3 through 8 as described previously in Creating a Temporary Cold Weather Shelter.

16

BRIGGSandSTRATTON.COM

Image 16
Contents Operator’s Manual Manual No GS Revision a 02/25/2009Where to Find Us GeneratorEngine Date PurchasedTable of Contents Operator Safety Important Safety InformationSafety Symbols and Meanings Equipment DescriptionMonoxide, an odorless, colorless, poison gas Nausea, fainting or deathHydrogen gas during recharging Fire or explosion can cause severe burns or deathWhen Testing for Engine Spark Fuel tank causing a fireExcessively low speeds impose a heavy load Assembly Install Wheel KitShipment Contents Unpack GeneratorTo install Attach Negative Battery CableTip generator so that engine end is up Add Engine Oil Add FuelFuel must meet these requirements High AltitudeConnecting to a Building’s Electrical System System GroundGenerator Location Special RequirementsFeatures and Controls Recoil Starter Used to start the engine manuallyNema L14-30 Cord Sets and ReceptaclesNema L5-30 Ground Fault Protection Battery ChargerTest Gfci Circuit Breaker Test your Gfci circuit breaker every month, as followsOperation Connecting Electrical LoadsStarting the Engine Charging a Battery Stopping the EngineOperating Automatic Idle Control Oil Pressure ShutdownCreating a Temporary Cold Weather Shelter Cold Weather OperationBuilding a Cold Weather Shelter Don’t Overload Generator Wattage Reference GuideMaintenance Maintenance ScheduleGenerator Maintenance Battery MaintenanceFuel Valve Maintenance Engine MaintenanceOil Recommendations Checking Oil LevelService Air Cleaner To service the air cleaner, follow these stepsService Spark Plugs Changing Engine Oil and FilterClean and inspect the spark arrester as follows Clean Cooling SystemCarburetor Adjustment Inspect Muffler and Spark ArresterStorage Generator StorageLong Term Storage Instructions Change Engine OilTroubleshooting BRIGGSandSTRATTON.COM Page Your Warranty Rights And Obligations Manufacturer’s Warranty CoverageOwner’s Warranty Responsibilities Briggs & Stratton Emissions Control Warranty ProvisionsWarranty on emissions-related parts is as follows ModerateIntermediate ExtendedLimited Warranty Reserved Common Service Parts Product Specifications800 Manual del Operario Dónde encontrarnos GeneradorMotor Fecha de compraResolución de problemas Garantías Seguridad de operarioMontaje Controles y característicasSeguridad de operario Descripción del equipoInformación importante de seguridad Símbolos sobre la seguridad y significadosCuando Anada Combustible O Vacíe EL Depósito Cuando Ponga EN Funcionamiento EL EquipoNo arranque el motor sin la bujía instalada Cuando Opere EL EquipoCuando Pruebe LA Bujía DEL Motor Cuando Ajuste O Haga Reparaciones a SU Máquina GeneradorNo modifique al generador en ninguna forma Montaje Desembalaje del generadorContenido de la caja Instale el juego de ruedasSuba el asas e inserte su pasador para mover el generador Conecte el cable negativo de la bateríaPara instalar Agregar aceite al motor Agregue combustibleEl combustible debe reunir los siguientes requisitos Gran altitudTierra del sistema Conexión al sistema eléctrico de un edificioUbicación del generador Requisitos especialesControles y características Amperios, monofásica de 60 HzTomacorriente con Dispositivo de Seguridad de Culatazo el Principio Usó para comenzar motor manualmenteJuego de Cable de 3 Alambres Juegos de cordones y enchufes conectoresNeutro Cargado Tierra Verde Protección contra fallos de conexión a tierra Cargador de bateríaEncienda el motor OperandoSi el motor no arranca, repita los pasos desde 4 hasta Conexión de cargas eléctricas Parada del motorFuncionamiento del control automático de marcha en vacío Parada por falta de presión de aceiteOperación durante un clima frío Carga de la bateriaLimpie los terminales de la batería si es necesario Page No sobrecargar el generador CapacidadEjemplo Control de la energíaMantenimiento Plan de mantenimientoMantenimiento del generador Mantenimiento de la bateríaMantenimiento de la válvula de combustible Mantenimiento del motorInstale el varilla de medición, apriete firmemente Cambio de aceite del motor y filtroColoque el tapón de vaciado y apriételo bien Quite la varilla de nivel de aceiteServicio del bujía Inspeccione el silenciador y la pantalla apagachispasLimpie e inspeccione el apagachispas de la siguiente manera Sistema de refrigeración de aireAlmacenamiento GeneradorAlmacenamiento para periodos prolongados Cambio de AceiteResolución de problemas Problemo Causa AccionGarantías Cobertura de la garantía del fabricanteResponsabilidades de la garantía del propietario Conectores y unidades Duración de la coberturaBRIGGSandSTRATTON.COM Garantía Limitada Especificaciones del producto Servicio común despideManuel d’utilisation Où nous trouver GénératriceMoteur Date d’achatFonctions et commandes Sécurité de l’opérateurAssemblage OpérationSymboles de sécurité et leur signification Sécurité de l’opérateurDescription de l équipement Renseignements importants de sécuritéExplosives Lors DE Lajout OU DE LA Vidange DU CarburantLors DU Démarrage DE Léquipement Lorsque Léquipement FonctionneAvertissement Le génératrice produit une tension élevée NE Touchez PAS les fils dénudés ou les boîtiersLorsque Vous Réglez OU Réparez Votre Génératrice Lors DE Tests Dallumage DU MoteurInstalle la roue la trousse AssemblageDéballez la génératrice Contenu de l’expéditionInstallation Raccordez le câble de retour de la batterieReplacez la génératrice à sa positon normale sur les roues Rattachez la vis au terminal négative de pile et serrezAjoutez de lhuile à moteur Ajoutez de lessence’essence satisfait les exigences suivantes Avis Évitez d’endommager le génératriceEmplacement de la génératrice Mise à la terre du systèmeExigences spéciales Dégagement de la génératriceFonctions et commandes Chargeur à tampon de batterie Utilisez la prise du chargeurCordons et prises Et/ou des dommages matérielsProtection contre les fuites de terre Chargeur de batterieMise à lessai du disjoncteur Gfci Pendant le fonctionnement de la génératriceOpération Démarrage du moteurBranchement des charges électriques Arrêt du moteurFonctionnement du contrôle automatique du ralenti Arrêt du moteur en cas de bas niveau d’huileRecharge d’une batterie Fonctionnement par temps froidSi nécessaire, nettoyer les bornes de la batterie Protégez lunité contre les intempériesCréation d’un abri pour les temps froids Création d’un abri temporaire pour les temps froidsVent Exemple Ne pas surchargez générateurGestion de la consommation Calendrier dentretien EntretienEntretien de génératrice Huile Recommandations relatives à l’huile Entretien de la batterieEntretien de la vanne de combustible Entretien du moteurVérification du niveau dhuile Ajout d’huileChangement d’huile à moteur et de filtre Secondes pour laisser couler lhuileEntretien du filtre à air Décrochez les verrous a des deux côtés duEntretien de la bougies dallumage Inspectez le silencieux et l’écran pare-étincellesNettoyez et inspectez le pare-étincelles comme suit Remettez l’écran en place et fixez-le avec quatre visNettoyer le système de refroidissement Vérifier le jeu des soupapesEntreposage Entreposage de la génératriceChangement de lhuile Autres idées de remisageDépannage Garanties Vos droits et obligations relatifs à la garantieCouverture de garantie du fabricant Pièces garantiesCatégorie B = 250 heures Catégorie a = 500 heures Garantie Limitée Réservé Caractéristiques du produit Pièces d’entretien courant