INSTALLATION

Lifting the Generator

The generator weighs more than 280 pounds. Proper tools, equipment and qualified personnel should be used in all phases of handling and moving generator.

WARNING

Lifting Hazard / Heavy Object

Can cause muscle strain or back injury.

DO NOT lift or move generator without assistance.

DO NOT lift unit by roof as damage to generator will occur.

Lifting pockets are provided at each corner between the base of the generator and its mounting pad. Retouch any chipped paint with supplied touch-up paint.

Home Standby Generator Location

Before installing generator, consult with homeowner and convey the following guidelines which may affect the desired location.

WARNING

Exhaust heat/gases can ignite combustibles or structures causing a fire.

DO NOT install the generator closer than 5 feet (1.5m) from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.

Keep at least 3 ft. (91 cm) clearance on all sides of generator including overhead.

Generator Clearances

Install generator outdoors in an area which will not accumulate deadly exhaust gas. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area (Figure 1). Prevailing winds and air currents should be taken into consideration when positioning generator.

Figure 1 — Home Standby Generator Clearances

Exhaust

Port

WARNING

Running engine gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures, nausea, fainting or death.

Operate generator ONLY outdoors.

Install a battery operated carbon monoxide alarm near the bedrooms.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes, or other openings.

General Location Guidelines

Install the unit outdoors ONLY.

Place the unit in a prepared location that is flat and has provisions for water drainage.

Install the unit in a location where sump pump discharge, rain gutter down spouts, roof run-off, landscape irrigation, or water sprinklers will not flood the unit or spray the enclosure and enter any air inlet our outlet openings.

Install the unit where the location of any services such as phone, electrical, fuel, air conditioning, irrigation, including covered, concealed and underground services will not be affected or obstructed.

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, you may need to construct a windbreak to protect the unit.

Install the generator as close as possible to the fuel supply to reduce length of pipes.

IMPORTANT: Laws or local codes may regulate the distance to the fuel supply.

The Home Standby Generator is shipped already attached to its mounting pad. Unless mandated by local code, a concrete slab is not required.

If mandated by local code, construct a concrete slab at least 3 inches thick and 6 inches longer and wider than the unit. Attach unit to slab with 1/4” diameter (minimum) masonry anchor bolts long enough to retain the unit.

10

Image 10 Contents
Rated Watts Home Generator System Table of Contents Engine exhaust from this product contains Important Safety InstructionsHazard Symbols and Meanings Certain components in this product and relatedSafety Rules Installing the 15A fuse could cause the engine to start Know Your Home Standby Generator Battery Control Panel see Know Your Control Panel AUTO/OFF/MANUALIntroduction Installer ResponsibilitiesInstallation Assistance Customer ResponsibilitiesInstallation Procedures Owner OrientationGenerator Clearances Lifting the GeneratorHome Standby Generator Location General Location GuidelinesEssential Circuit Selection Essential CircuitsDevice Running Watts Removable Roof and Access Door Fuel Inlet DimensionsDisconnect Box Mounting Guidelines Gaseous Fuel System Do not light a cigarette or smokeTemporary Manometer Installed Fuel Consumption10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft Fuel Pipe Sizing10ft Withdrawal Rate 32F 20F 10F 30F 40F Fuel Comparison ChartPhysical Properties Propane Natural Gas Wire Connections Before Initial START-UPBattery posts, terminals and related accessories contain Battery ConnectionCharging the Battery Servicing the BatteryAutomatic Operation Sequence Fuel System SelectionInitial START-UP no Load Fuel Supply SystemEngine Cool-down Timer Setting Exercise TimerInstallation Inspection To perform the Set Exercise procedureAutomatic Operation SpecificationsFault Detection System Checking Automatic OperationNo LED Discharged Battery Fault DescriptionReset Fault Detection System Low Oil PressureChanging Oil Generator MaintenanceChanging Engine Oil and Filter Changing Oil FilterWhen Calling the Factory To Clean the GeneratorStorage Down when loads are connected TroubleshootingProblem Cause Correction AvailableSchematic Wiring Diagram Page Limited Warranty Tabla DE Contenido Sensor de Excitación de Tensión de la CompañíaDeterminados componentes en este producto y los AdvertenciaSímbolos de Peligro y Significados Gases Tóxicos Manual de OperarioLos generadores producen un voltaje muy poderoso Precaución Instala el fusible se puede producir el arranque del motorFiltro de Aceite Salida del Escape Conozca SU Generador DE ReservaEtiqueta del Motor Manguera de Drenaje de Aceite Etiqueta deConozca EL Panel DE Control DisyuntorResponsabilidades DEL Instalador Conserve Estas InstruccionesIntroducción Responsabilidades DEL ClienteProcedimientos DE Instalación Distancias Desde el Generador Elevación del GeneradorUbicación del Generador de Reserva Pautas Generales para la Ubicación del GeneradorSelección de los Circuitos Fundamentales Circuitos FundamentalesDispositivo Vatiaje de Directrices de Montaje del Cuadro de Desconexión Dimensiones de la Entrada de CombustibleTecho y Puerta de Acceso Desmontables Sistema DE Combustible Gaseoso Al generador de Reserva Consumo de CombustibleGas Natural Vapor de PL Gas Natural peso específico = Dimensiones de la Cañería de CombustiblePropano Líquido PL peso específico = Propiedades físicas Propano Gas natural Cuadro de Comparación de CombustiblesTasa de consumo 32F 20F 10F 30F 40F Conexiones DE Cables Antes DEL Arranque InicialFije el interruptor AUTO/OFF/MANUAL en la posición Auto Conexión de la BateríaInstale el fusible de 15 Amperios en el panel de control Servicio la BateríaSecuencia DE Operación Automática Selección DEL Sistema DE CombustibleArranque Inicial SIN Carga Sistema de Suministro de CombustibleInspección Posterior a LA Instalación Temporizador de enfriamiento del motorSistema DE Detección DE Fallas EspecificacionesOperación Automática Verificación de la Operación AutomáticaLas patillas de las baterías, los terminales y los Cambio del Filtro de Aceite Mantenimiento DEL GeneradorCambio del Aceite del Motor y del Filtro Cambio del AceitePara Limpiar el Generador AlmacenamientoSi Llama a la Fábrica Reparacion DE Averias Notas Garantía Limitada Table DES Matières Veuillez Conserver CES Instructions Symboles de Danger et MoyensAvertissement NE touchez PAS les fils dénudés ou les boîtiers Avis FAMILIARISEZ-VOUS Avec Votre Génératrice D’ÉTAT D’ATTENTE Filtre à Air Et Jauge dHuile Filtre à lHuile15 Ampères FAMILIARISEZ-VOUS Avec LE Tableau DE CommandeFusible de DisjoncteurConservez CES Instructions Responsabilités DE LinstallateurAide À Linstallation IntroductionProcédures Dinstallation Conseils AU PropriétaireSoulèvement de la Génératrice Emplacement du Génératrice d’état d’AttenteDirectives Générales Concernant lEmplacement Dégagement Autour de la GénératriceSélection des Circuits Essentiels Circuits EssentielsAppareil Watts Directives dAssemblage du Boîtier de Débranchement Dimensions de lOrifice dAdmission du CombustibleToit Amovible et Porte dAccès LE Système DE Combustible Gazeux Vers le génératrice ’état d’attente Consommation de CombustibleIl faudrait inclure une sortie pour manomètre Gas Naturel Vapeur PLGrosseur du Tuyau de Combustible Gaz de Pétrole Liquéfié GPL densité = 1,5032F 20F 10F 30F 40F Charte de Comparaison des CombustiblesPropriétés physiques Propane Gaz naturel 12,2 C 17,8 C 23,3 C 34,4 C 40 CRaccords DE Fils Avant LE Démarrage InitialRéglez linterrupteur AUTO/OFF/MANUAL sur Auto Branchement de la BatterieRechargez la Batterie Entretien de la BatterieSystème dAlimentation en Combustible Sélection DU Système DE CombustibleDémarrage Initial Sans Charge Réglez linterrupteur AUTO/OFF/MANUAL sur ManualRéglage DE LA Minuterie DU Cycle Dexercice Vérification InstallationCapteur de Prise en Charge de la Tension de Service Minuterie de Refroidissement du MoteurSystème DE Détection DES Pannes CaractéristiquesFonctionnement Automatique Entretien du SystèmeAucun DEL Batterie déchargée Nombre de Clignotements Du VoyantRéarmement du Système de Détection des Pannes Faible Pression dHuileVidange de lHuile Entretien DU GénérateurChangement dHuile à Moteur et de Filtre Changement du filtre à huilePour Nettoyer le Générateur RemisageCommunications avec le Fabricant Dépannage Garantie Limitée