INSTALLATION

Essential Circuits

Consult with owner to clearly identify the circuits in building that are "essential".

It is important that you understand which circuits the owner wants to include as "Essential Circuits". Depending on the power consumed by these circuits, most or all of them can be switched to the Home Standby Generator for the duration of normal power interruption.

The wattage reference guide shown in Figure 2 will assist the owner with their decision-making process. It provides the wattage used by many ordinary household devices. Use it as a guide when selecting essential circuits. Review this information with the owner and convey any technical considerations that might affect the cost of installation.

Essential Circuit Selection

When selecting the essential circuits that will be switched to “Standby Power,” it is important that the sum of the combined circuit loads does not exceed the wattage/amperage capacity of the generator. To help you with your selection of essential circuits, please consider the following:

Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the generator’s wattage capacity.

The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.

If the appliance, tool or motor nameplate does not list wattage, multiply volts times the ampere rating to determine watts (Volts x Amps = Watts).

Some electric motors (induction types) require about three times more watts of power for starting than for running. This surge lasts for only a few seconds. Be sure you allow for this high starting wattage when selecting electrical devices that will be energized by the Home Standby Generator:

Figure the watts required to start the largest motor.

Add that to the total running watts of all other connected loads.

This Briggs & Stratton Home Standby Generator complies with the following “stationary standby power rating”:

The standby power rating is applicable for supplying power for the duration of normal power interruption. NO sustained overload capability is available for this rating.

Figure 2 — Wattage Reference Guide

 

Device

Running

 

Watts

 

 

 

Air Conditioner (12,000 Btu)*

1700

 

Air Conditioner (24,000 Btu)*

3800

 

Air Conditioner (40,000 Btu)*

6000

 

Battery Charger (20 Amp)

500

 

Circular Saw (6-1/2")

800 to 1000

 

Clothes Dryer (Electric)*

5750

 

Clothes Dryer (Gas)*

700

 

Clothes Washer*

1150

 

Coffee Maker

1750

 

Compressor (1 HP)*

2000

 

Compressor (1/2 HP)*

1400

 

Compressor (3/4 HP)*

1800

 

Curling Iron

700

 

Dehumidifier*

650

 

Electric Blanket

400

 

Electric Range (per element)

1500

 

Electric Skillet

1250

 

Freezer*

700

 

Furnace Fan (3/5 HP)*

875

 

Garage Door Opener*

500 to 750

 

Hair Dryer

1200

 

Hand Drill

250 to 1100

 

Iron

1200

 

Jet Pump*

800

 

Light Bulb

100

 

Microwave Oven

700 to 1000

 

Milk Cooler*

1100

 

Oil Burner on Furnace

300

 

Oil Fired Space Heater (140,000 Btu)

400

 

Oil Fired Space Heater (30,000 Btu)

150

 

Oil Fired Space Heater (85,000 Btu)

225

 

Radio

50 to 200

 

Refrigerator

700

 

Slow Cooker

200

 

Submersible Pump (1 HP)*

2000

 

Submersible Pump (1/2 HP)*

1500

 

Submersible Pump (1-1/2 HP)*

2800

 

Sump Pump*

800 to 1050

 

Table Saw (10")*

1750 to 2000

 

Television

200 to 500

 

Toaster

1000 to 1650

*Allow three (3) times listed watts for starting device

11

Image 11 Contents
Rated Watts Home Generator System Table of Contents Certain components in this product and related Important Safety InstructionsHazard Symbols and Meanings Engine exhaust from this product containsSafety Rules Installing the 15A fuse could cause the engine to start Control Panel see BatteryKnow Your Home Standby Generator AUTO/OFF/MANUAL Know Your Control PanelCustomer Responsibilities Installer ResponsibilitiesInstallation Assistance IntroductionOwner Orientation Installation ProceduresGeneral Location Guidelines Lifting the GeneratorHome Standby Generator Location Generator ClearancesDevice Running Watts Essential CircuitsEssential Circuit Selection Disconnect Box Mounting Guidelines Fuel Inlet DimensionsRemovable Roof and Access Door Do not light a cigarette or smoke Gaseous Fuel SystemFuel Consumption Temporary Manometer Installed10ft Fuel Pipe Sizing10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft Physical Properties Propane Natural Gas Fuel Comparison ChartWithdrawal Rate 32F 20F 10F 30F 40F Before Initial START-UP Wire ConnectionsServicing the Battery Battery ConnectionCharging the Battery Battery posts, terminals and related accessories containFuel Supply System Fuel System SelectionInitial START-UP no Load Automatic Operation SequenceTo perform the Set Exercise procedure Setting Exercise TimerInstallation Inspection Engine Cool-down TimerChecking Automatic Operation SpecificationsFault Detection System Automatic OperationLow Oil Pressure Fault DescriptionReset Fault Detection System No LED Discharged BatteryChanging Oil Filter Generator MaintenanceChanging Engine Oil and Filter Changing OilStorage To Clean the GeneratorWhen Calling the Factory Available TroubleshootingProblem Cause Correction Down when loads are connectedSchematic Wiring Diagram Page Limited Warranty Sensor de Excitación de Tensión de la Compañía Tabla DE ContenidoGases Tóxicos Manual de Operario AdvertenciaSímbolos de Peligro y Significados Determinados componentes en este producto y losLos generadores producen un voltaje muy poderoso Instala el fusible se puede producir el arranque del motor PrecauciónManguera de Drenaje de Aceite Etiqueta de Conozca SU Generador DE ReservaEtiqueta del Motor Filtro de Aceite Salida del EscapeDisyuntor Conozca EL Panel DE ControlResponsabilidades DEL Cliente Conserve Estas InstruccionesIntroducción Responsabilidades DEL InstaladorProcedimientos DE Instalación Pautas Generales para la Ubicación del Generador Elevación del GeneradorUbicación del Generador de Reserva Distancias Desde el GeneradorDispositivo Vatiaje de Circuitos FundamentalesSelección de los Circuitos Fundamentales Techo y Puerta de Acceso Desmontables Dimensiones de la Entrada de CombustibleDirectrices de Montaje del Cuadro de Desconexión Sistema DE Combustible Gaseoso Gas Natural Vapor de PL Consumo de CombustibleAl generador de Reserva Propano Líquido PL peso específico = Dimensiones de la Cañería de CombustibleGas Natural peso específico = Tasa de consumo 32F 20F 10F 30F 40F Cuadro de Comparación de CombustiblesPropiedades físicas Propano Gas natural Antes DEL Arranque Inicial Conexiones DE CablesServicio la Batería Conexión de la BateríaInstale el fusible de 15 Amperios en el panel de control Fije el interruptor AUTO/OFF/MANUAL en la posición AutoSistema de Suministro de Combustible Selección DEL Sistema DE CombustibleArranque Inicial SIN Carga Secuencia DE Operación AutomáticaTemporizador de enfriamiento del motor Inspección Posterior a LA InstalaciónVerificación de la Operación Automática EspecificacionesOperación Automática Sistema DE Detección DE FallasLas patillas de las baterías, los terminales y los Cambio del Aceite Mantenimiento DEL GeneradorCambio del Aceite del Motor y del Filtro Cambio del Filtro de AceiteSi Llama a la Fábrica AlmacenamientoPara Limpiar el Generador Reparacion DE Averias Notas Garantía Limitada Table DES Matières Avertissement Symboles de Danger et MoyensVeuillez Conserver CES Instructions NE touchez PAS les fils dénudés ou les boîtiers Avis Filtre à Air Et Jauge dHuile Filtre à lHuile FAMILIARISEZ-VOUS Avec Votre Génératrice D’ÉTAT D’ATTENTEDisjoncteur FAMILIARISEZ-VOUS Avec LE Tableau DE CommandeFusible de 15 AmpèresIntroduction Responsabilités DE LinstallateurAide À Linstallation Conservez CES InstructionsConseils AU Propriétaire Procédures DinstallationDégagement Autour de la Génératrice Emplacement du Génératrice d’état d’AttenteDirectives Générales Concernant lEmplacement Soulèvement de la GénératriceAppareil Watts Circuits EssentielsSélection des Circuits Essentiels Toit Amovible et Porte dAccès Dimensions de lOrifice dAdmission du CombustibleDirectives dAssemblage du Boîtier de Débranchement LE Système DE Combustible Gazeux Gas Naturel Vapeur PL Consommation de CombustibleIl faudrait inclure une sortie pour manomètre Vers le génératrice ’état d’attenteGaz de Pétrole Liquéfié GPL densité = 1,50 Grosseur du Tuyau de Combustible12,2 C 17,8 C 23,3 C 34,4 C 40 C Charte de Comparaison des CombustiblesPropriétés physiques Propane Gaz naturel 32F 20F 10F 30F 40FAvant LE Démarrage Initial Raccords DE FilsEntretien de la Batterie Branchement de la BatterieRechargez la Batterie Réglez linterrupteur AUTO/OFF/MANUAL sur AutoRéglez linterrupteur AUTO/OFF/MANUAL sur Manual Sélection DU Système DE CombustibleDémarrage Initial Sans Charge Système dAlimentation en CombustibleMinuterie de Refroidissement du Moteur Vérification InstallationCapteur de Prise en Charge de la Tension de Service Réglage DE LA Minuterie DU Cycle DexerciceEntretien du Système CaractéristiquesFonctionnement Automatique Système DE Détection DES PannesFaible Pression dHuile Nombre de Clignotements Du VoyantRéarmement du Système de Détection des Pannes Aucun DEL Batterie déchargéeChangement du filtre à huile Entretien DU GénérateurChangement dHuile à Moteur et de Filtre Vidange de lHuileCommunications avec le Fabricant RemisagePour Nettoyer le Générateur Dépannage Garantie Limitée