Briggs & Stratton 040220A manual Fault Description, Reset Fault Detection System, Low Oil Pressure

Page 22

OPERATION

Number of LED Flashes

Fault Description

2

Low oil pressure

4

Engine failed to start

5

Low frequency

6

Engine overspeed

Reset Fault Detection System

The operator must reset the fault detection system each time it activates. To do so, place the AUTO/OFF/MANUAL switch in the OFF position for 30 seconds or more. Return the Home Standby Generator to service after correcting the problem by placing the AUTO/OFF/MANUAL switch in the AUTO position.

A description of each fault and suggested remedies are as follows:

No LED - Discharged Battery

This condition is caused by a completely discharged battery. To remedy the problem, remove the 15 Amp fuse and disconnect the battery from the generator. Take the battery to a local battery store for analysis.

Install the battery after it has been fully recharged or replaced, connecting the NEGATIVE cable last. Install the 15 Amp fuse.

WARNING

Battery posts, terminals and related accessories contain

lead and lead compounds - chemicals known to the State of California to cause cancer and reproductive harm. Wash hands after handling.

Low Oil Pressure

This fault is indicated by two blinks. The generator is equipped with an oil pressure switch (Figure 11). Should oil pressure drop, switch contacts close and the engine is shut down.

Figure 11 — Low Oil Pressure

Oil Pressure Switch

To remedy the low oil pressure condition, add the recommended oil to the FULL mark on the dipstick.

If low oil pressure condition still exists, generator will start, then shut down after approximately 10 seconds and diagnostic LED will flash. In this case, contact your local service center.

Engine Fail To Start

This fault is indicated by four blinks. This feature prevents the generator from damage by continually attempting to start. Each time the system is directed to start, the generator will crank for 15 seconds, pause for 15 seconds, crank for

15 seconds, pause for 15 seconds, and repeat. If the generator does not begin producing electricity after approximately 90 seconds, the generator will stop cranking and the LED will blink.

The most likely cause of this problem is no fuel supply. Check the inside and outside fuel shut off valves to ensure they are fully open. Other causes could be failed spark plug, failed engine ignition, or the engine air filter is clogged. You may need to contact your local service center for assistance if you can’t remedy these problems.

Low Frequency

This fault is indicated by five blinks. This feature protects devices connected to the transfer switch by shutting the generator down if the engine runs slower than the preset limit.

This condition may be potentially caused by a failed engine governor. To remedy the problem, you should contact your local service center for assistance.

This condition may also be potentially caused by excessive loads on the generator. Turn off devices one at a time and check the frequency. To remedy the problem, you may need to contact your local service center for assistance.

Engine Overspeed

This fault is indicated by six blinks. This feature protects devices connected to the transfer switch by shutting the generator down if the engine happens to run faster than the preset limit. The overspeed fault is detected as follows:

If the generator output frequency runs at 72 Hz for five seconds, the generator will shut down.

If the generator output frequency reaches 75 Hz, the generator will shut down immediately.

This condition is potentially caused by a failed engine governor. To remedy the problem, you should contact your local service center for assistance.

22

Image 22 Contents
Rated Watts Home Generator System Table of Contents Engine exhaust from this product contains Important Safety InstructionsHazard Symbols and Meanings Certain components in this product and relatedSafety Rules Installing the 15A fuse could cause the engine to start Know Your Home Standby Generator BatteryControl Panel see Know Your Control Panel AUTO/OFF/MANUALIntroduction Installer ResponsibilitiesInstallation Assistance Customer ResponsibilitiesInstallation Procedures Owner OrientationGenerator Clearances Lifting the GeneratorHome Standby Generator Location General Location GuidelinesEssential Circuit Selection Essential CircuitsDevice Running Watts Removable Roof and Access Door Fuel Inlet DimensionsDisconnect Box Mounting Guidelines Gaseous Fuel System Do not light a cigarette or smokeTemporary Manometer Installed Fuel Consumption10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft Fuel Pipe Sizing10ft Withdrawal Rate 32F 20F 10F 30F 40F Fuel Comparison ChartPhysical Properties Propane Natural Gas Wire Connections Before Initial START-UP Battery posts, terminals and related accessories contain Battery Connection Charging the Battery Servicing the BatteryAutomatic Operation Sequence Fuel System SelectionInitial START-UP no Load Fuel Supply SystemEngine Cool-down Timer Setting Exercise TimerInstallation Inspection To perform the Set Exercise procedureAutomatic Operation SpecificationsFault Detection System Checking Automatic OperationNo LED Discharged Battery Fault DescriptionReset Fault Detection System Low Oil PressureChanging Oil Generator MaintenanceChanging Engine Oil and Filter Changing Oil FilterWhen Calling the Factory To Clean the GeneratorStorage Down when loads are connected TroubleshootingProblem Cause Correction AvailableSchematic Wiring Diagram Page Limited Warranty Tabla DE Contenido Sensor de Excitación de Tensión de la CompañíaDeterminados componentes en este producto y los AdvertenciaSímbolos de Peligro y Significados Gases Tóxicos Manual de OperarioLos generadores producen un voltaje muy poderoso Precaución Instala el fusible se puede producir el arranque del motorFiltro de Aceite Salida del Escape Conozca SU Generador DE ReservaEtiqueta del Motor Manguera de Drenaje de Aceite Etiqueta deConozca EL Panel DE Control DisyuntorResponsabilidades DEL Instalador Conserve Estas InstruccionesIntroducción Responsabilidades DEL ClienteProcedimientos DE Instalación Distancias Desde el Generador Elevación del GeneradorUbicación del Generador de Reserva Pautas Generales para la Ubicación del GeneradorSelección de los Circuitos Fundamentales Circuitos FundamentalesDispositivo Vatiaje de Directrices de Montaje del Cuadro de Desconexión Dimensiones de la Entrada de CombustibleTecho y Puerta de Acceso Desmontables Sistema DE Combustible Gaseoso Al generador de Reserva Consumo de CombustibleGas Natural Vapor de PL Gas Natural peso específico = Dimensiones de la Cañería de CombustiblePropano Líquido PL peso específico = Propiedades físicas Propano Gas natural Cuadro de Comparación de CombustiblesTasa de consumo 32F 20F 10F 30F 40F Conexiones DE Cables Antes DEL Arranque InicialFije el interruptor AUTO/OFF/MANUAL en la posición Auto Conexión de la BateríaInstale el fusible de 15 Amperios en el panel de control Servicio la BateríaSecuencia DE Operación Automática Selección DEL Sistema DE CombustibleArranque Inicial SIN Carga Sistema de Suministro de CombustibleInspección Posterior a LA Instalación Temporizador de enfriamiento del motorSistema DE Detección DE Fallas EspecificacionesOperación Automática Verificación de la Operación AutomáticaLas patillas de las baterías, los terminales y los Cambio del Filtro de Aceite Mantenimiento DEL GeneradorCambio del Aceite del Motor y del Filtro Cambio del AceitePara Limpiar el Generador AlmacenamientoSi Llama a la Fábrica Reparacion DE Averias Notas Garantía Limitada Table DES Matières Veuillez Conserver CES Instructions Symboles de Danger et MoyensAvertissement NE touchez PAS les fils dénudés ou les boîtiers Avis FAMILIARISEZ-VOUS Avec Votre Génératrice D’ÉTAT D’ATTENTE Filtre à Air Et Jauge dHuile Filtre à lHuile15 Ampères FAMILIARISEZ-VOUS Avec LE Tableau DE CommandeFusible de DisjoncteurConservez CES Instructions Responsabilités DE LinstallateurAide À Linstallation IntroductionProcédures Dinstallation Conseils AU PropriétaireSoulèvement de la Génératrice Emplacement du Génératrice d’état d’AttenteDirectives Générales Concernant lEmplacement Dégagement Autour de la GénératriceSélection des Circuits Essentiels Circuits EssentielsAppareil Watts Directives dAssemblage du Boîtier de Débranchement Dimensions de lOrifice dAdmission du CombustibleToit Amovible et Porte dAccès LE Système DE Combustible Gazeux Vers le génératrice ’état d’attente Consommation de CombustibleIl faudrait inclure une sortie pour manomètre Gas Naturel Vapeur PLGrosseur du Tuyau de Combustible Gaz de Pétrole Liquéfié GPL densité = 1,5032F 20F 10F 30F 40F Charte de Comparaison des CombustiblesPropriétés physiques Propane Gaz naturel 12,2 C 17,8 C 23,3 C 34,4 C 40 CRaccords DE Fils Avant LE Démarrage InitialRéglez linterrupteur AUTO/OFF/MANUAL sur Auto Branchement de la BatterieRechargez la Batterie Entretien de la BatterieSystème dAlimentation en Combustible Sélection DU Système DE CombustibleDémarrage Initial Sans Charge Réglez linterrupteur AUTO/OFF/MANUAL sur ManualRéglage DE LA Minuterie DU Cycle Dexercice Vérification InstallationCapteur de Prise en Charge de la Tension de Service Minuterie de Refroidissement du MoteurSystème DE Détection DES Pannes CaractéristiquesFonctionnement Automatique Entretien du SystèmeAucun DEL Batterie déchargée Nombre de Clignotements Du VoyantRéarmement du Système de Détection des Pannes Faible Pression dHuileVidange de lHuile Entretien DU GénérateurChangement dHuile à Moteur et de Filtre Changement du filtre à huilePour Nettoyer le Générateur RemisageCommunications avec le Fabricant Dépannage Garantie Limitée