Tripp Lite SU20KX, SU80KX, SU40KX owner manual Internal Battery Connection Procedure

Page 13

6 – Internal Battery Connection (continued)

1

6-2 Internal Battery Connection Procedure

1 Place the UPS system in bypass (or turn it completely off) and turn off the internal battery circuit breaker switch, located on the rear of the UPS system.

2 Remove the battery access bezels, located on the front of the UPS system.

3 Remove the battery cartridge fuses from each fuse block.

4 Disconnect the blue and white jumper cables attached to each fuse

block. Warning: When disconnecting the jumper cables, pull them straight away from the fuse block with even force. Do not wiggle them side-to-side, as this may damage the connector.

5 Remove the fuse block bracket. Note its orientation before removal.

 

2

 

3

1

4

 

5

6

2

7

8

3

9

10

11

4

12

13

5

14

13

Image 13
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesLocation Warnings Important Safety InstructionsConnection Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Preparation Cabinet InstallationUnpacking Shipping container. Warning The UPS system could tip if it PlacementRear, not from the sides Rear of the UPS systemSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring Failure to observe proper phase will damage the UPS system AC Input/Output Wiring Single UPSCreate a risk of personal injury and property damage Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input SourceBattery Backup Mode Single UPS Online Normal Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSBattery Backup Mode Parallel UPS Online Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSPreliminary Checklist Single UPS Control Panel and Breaker DiagramsStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Control Panel Diagram Display and ConfigurationDisplay Hierarchy Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel Group Parallel SetupParallel ID Battery Auto Test Control & Test SetupBuzzer Clear Battery Test Result Manual Battery TestForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatUser Password Administrator PasswordLanguage Firmware Version MaintenanceStatistics Advance Use or to read the event log, then press toCommunications Interfaces CommunicationsSnmpwebcard Slot Input Dry Contact Interface Auxiliary Dry Contact Input Circuit Diagram Remote Emergency Power Off EPO Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputOutput Dry Contact Interface Detail Default MessagesOptional Messages 11-10 RS-232 Serial Port Circuit Diagram Output Dry Contact Circuit DiagramParallel Configuration Port Hardware Pin AssignmentUPS System Technical Specifications Optional Messages SpecificationsWarranty Storage and ServiceService Storage