Tripp Lite SU40KX, SU80KX, SU20KX owner manual Battery Start-Up Procedure Single UPS

Page 26

19 – Start-Up, Shutdown and Bypass (continued)

9-3 Standard Start-Up Procedure (Single UPS) (continued)

2 3

3

4

4

5

5

6

7

Switch on the bypass input breaker switch Q2 and then output circuit breaker switch Q4 . After a brief initialization process, the LCD screen will show “ON AUTO BYPASS”, the “BYPASS” LED will illuminate and UPS system output will be supplied by the bypass (reserve) power source.

Switch on the main input circuit breaker switch Q1 . If the AC input power source is normal, the UPS system is ready for start-up.

Press the ON button A for 3 seconds (until you hear a beep), then release the button. The inverter will activate and synchronize with the bypass source, then automatically switch from auto bypass (reserve) mode to online (normal) mode. The “BYPASS” LED will darken and the “NORMAL” LED will illuminate.

Q4

 

Q2

 

Output

Manual

Bypass

Main

3

Bypass

Input

Input

 

 

 

 

 

 

Q1

Output

Manual

Bypass

Main

4

Bypass

Input

Input

 

 

 

 

 

 

A

5

89-4 Battery Start-Up Procedure (Single UPS)

Note: The battery must be at least partially charged for this operation to succeed.

 

 

 

If there is an external battery cabinet connected, switch on the

 

 

1

 

 

 

 

circuit breaker

A

of the external battery cabinet. On the SU20KX

9

 

 

or SU40KX, turn on the battery breaker on the back of the UPS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

Confirm that the manual bypass circuit breaker switch

 

is off.

 

 

 

 

 

 

2

Q3

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

Press the ON button

 

for 3 seconds (until you hear a beep), then

 

A

 

 

3

 

 

 

release the button. The inverter will activate and use stored DC

13

 

 

battery power to supply AC power to connected equipment. The

 

 

“BATTERY” LED will illuminate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

1

Q3

Output

Manual

Bypass

Main

2

Bypass

Input

Input

 

 

 

 

 

 

A

3

 

 

 

26

Image 26
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionConnection Warnings Important Safety InstructionsLocation Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Rear, not from the sides PlacementShipping container. Warning The UPS system could tip if it Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsAuto Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSStandard Start-Up Procedure Single UPS Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Use or to read the event log, then press to AdvanceSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces External Battery Cabinet Temperature Inputs Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Status InputOptional Messages Default MessagesOutput Dry Contact Interface Detail Parallel Configuration Port Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesService Storage and ServiceWarranty Storage