Tripp Lite SU20KX, SU80KX, SU40KX owner manual Manual Bypass Procedure Parallel UPS

Page 31

9 – Start-Up, Shutdown and Bypass (continued)

 

1

 

 

 

 

9-10 Manual Bypass Procedure (Parallel UPS)

 

 

 

Warning: When the UPS system is in manual bypass, the inverter shuts down. Connected equipment loads are powered by the bypass

2

(reserve) power source and will not receive battery backup during a utility power failure.

1 For the first UPS system you wish to shut down, press the OFF

 

 

 

 

 

 

 

button A for 3 seconds (until you hear a beep), then release

 

 

 

 

 

 

 

the button. If the other UPS system can support the connected

 

 

 

 

 

 

 

equipment loads alone, the UPS system that was turned off will

 

 

 

 

 

3

 

shut down its inverter and its LCD screen will read “LOAD NOT

 

 

 

 

 

 

 

 

 

 

 

 

 

POWERED”. The other UPS system’s LCD screen will read

 

 

 

 

 

 

 

“ONLINE MODE”. If the total connected equipment load is too

 

 

 

 

 

 

 

large to be handled by a single UPS system, both UPS systems

 

 

 

 

A

 

 

will shut down their inverters and switch to bypass mode, and their

1

 

 

 

4

 

 

 

 

 

 

LCD screens will read “ON AUTO BYPASS”. Repeat step 1 for

 

 

 

 

 

 

 

the second UPS system you wish to shut down.

 

 

 

 

 

 

2

Switch off the main input circuit breaker switch Q1 of each UPS

 

 

 

 

 

 

 

system.

 

 

 

 

Q1

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Manual

Bypass

Main

 

 

 

2

 

Bypass

Input

Input

6

 

 

 

 

 

 

3

Confirm that both UPS systems are shut down, then switch on

 

 

 

 

 

 

 

 

 

 

 

 

the manual bypass input circuit breaker switch Q3 of each UPS

 

 

 

 

 

 

 

system. The bypass (reserve) power source will power the loads

 

 

 

 

 

 

 

and the LCD screen will read “ON MANUAL BYPASS”.

 

 

Q3

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Manual

Bypass

Main

 

 

 

3

 

Bypass

Input

Input

8

 

 

 

 

 

 

4

Switch off the bypass input circuit breaker switch Q2 and the

 

 

 

 

 

 

output circuit breaker switch Q4 of each UPS system. The LCD

 

 

 

 

 

 

 

screen will turn off completely.

 

 

 

 

 

 

 

 

 

Q4

 

Q2

 

9

 

 

 

 

 

 

 

 

 

 

Output

Manual

Bypass

Main

 

 

 

4

 

Bypass

Input

Input

 

 

 

 

 

 

 

10

5 If the UPS systems have external battery cabinets connected,

 

 

 

 

 

 

switch off the external battery cabinet circuit breaker switch A

 

 

A

 

 

 

 

of each battery pack. On the SU20KX or SU40KX, turn OFF the

 

 

 

 

 

 

battery breaker on the back of the UPS.

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

5

 

 

 

 

 

6

In this mode, only the manual bypass path (including the manual

 

 

 

 

 

12

 

bypass circuit breaker Q3 ), the load terminals of the output

 

 

 

 

 

 

 

circuit breaker switch Q4 and the terminal block B contain

 

 

 

 

B

 

 

hazardous voltage, allowing qualified service personnel to perform

 

 

 

 

 

 

Q4

Q3

 

 

 

 

 

maintenance or repair. Note: Qualified service personnel may

 

 

 

 

 

 

 

 

 

 

13

 

prefer to de-energize the UPS systems completely, depending on

 

 

 

 

 

 

local codes and the nature of the maintenance or repair.

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

31

 

 

 

 

 

Image 31
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesLocation Warnings Important Safety InstructionsConnection Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Preparation Cabinet InstallationUnpacking Rear of the UPS system PlacementShipping container. Warning The UPS system could tip if it Rear, not from the sidesSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring Failure to observe proper phase will damage the UPS system AC Input/Output Wiring Single UPSCreate a risk of personal injury and property damage Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input Source10 8-4 Manual Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS Auto Bypass Mode Single UPSBattery Backup Mode Parallel UPS Online Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSStart-Up, Shutdown and Bypass Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Control Panel Diagram Display and ConfigurationDisplay Hierarchy Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel Group Parallel SetupParallel ID Battery Auto Test Control & Test SetupBuzzer Clear Battery Test Result Manual Battery TestForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatUser Password Administrator PasswordLanguage Firmware Version MaintenanceStatistics Advance Use or to read the event log, then press toCommunications Interfaces CommunicationsSnmpwebcard Slot Input Dry Contact Interface External Battery Status Input Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Cabinet Temperature InputsOutput Dry Contact Interface Detail Default MessagesOptional Messages Hardware Pin Assignment Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Parallel Configuration PortUPS System Technical Specifications Optional Messages SpecificationsStorage Storage and ServiceWarranty Service