Tripp Lite SU80KX, SU20KX Manual Bypass Procedure Single UPS, Shutdown Procedure Single UPS

Page 27

9 – Start-Up, Shutdown and Bypass (continued)

9-5 Manual Bypass Procedure (Single UPS)

1

Warning: Placing the UPS system in manual bypass will disable the inverter and power all loads from the manual bypass (reserve) source, but the UPS system will still be energized. Before performing maintenance or repair on the UPS system, shut down and de-energize the 2 UPS system completely by following the steps in Section 9-6. Although connected equipment loads will be powered by the bypass (reserve) power source, they will not receive battery backup in the event of a utility power failure.

1 If the UPS is in NORMAL mode (green LED ON, LCD displays “Load Protected – On Line Mode”), then you must stop the inverter by pressing and holding the red OFF (“O”) button A until the UPS beeps, then release the button and answer “YES” to the question “Transfer to Bypass Mode?”. The UPS should transfer to Bypass.

2 Confirm the UPS is in BYPASS mode (amber Bypass LED is ON; LCD displays “Load Unprotected – On Auto Bypass”). Do not proceed if it is not in BYPASS mode.

3 Turn OFF the MAIN INPUT circuit breaker Q1.

4 Wait until the Power Module fans turn OFF (this may take a minute or two), then turn OFF the BATTERY BREAKER. On the 40K unit, the BATTERY BREAKER (for the internal battery) is on the back of the UPS; on the 60K and 80K units, the BATTERY BREAKER is on the back of the matching battery cabinet. Note: Some external battery cabinets may have the BATTERY BREAKER behind the front door or elsewhere.

5 Turn ON the MANUAL BYPASS circuit breaker Q3. The LCD will display “Load Unprotected – On Manual Bypass” and you will hear an audible alarm.

6 Turn OFF the OUTPUT circuit breaker Q4.

7 Turn OFF the BYPASS INPUT circuit breaker Q2. The unit’s LCD will go blank after a few seconds.

8 The critical load is now supported by unconditioned utility power.

 

 

 

A

3

 

 

 

 

 

 

 

 

4

1

 

 

 

 

6

5

7

3

5

 

Q4

Q3

Q2

Q1

 

Output

Manual

Bypass

Main

6

 

3-7

Bypass

Input

Input

 

 

 

 

 

 

 

 

 

7

 

 

 

 

8

9-6 Shutdown Procedure (Single UPS)

Warning: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm that all loads

9

are turned off or place the UPS system in manual bypass mode to keep loads powered by the reserve (bypass) power source.

 

1 If the UPS is in NORMAL mode (green LED ON, LCD displays “Load Protected-On Line Mode”), then you must stop the inverter by pressing and holding the red OFF button A until the UPS beeps, then release the button. The UPS should transfer to Bypass.

2 Confirm the UPS is in BYPASS (amber Bypass LED is ON; LCD displays “Load Unprotected-On Auto Bypass”). Do not proceed if it is not on BYPASS.

3 Turn OFF the OUTPUT circuit breaker Q4.

4 Turn OFF the MAIN INPUT circuit breaker Q1.

5 Turn OFF the BYPASS UNIT circuit breaker Q2.

6 Wait until the Power Module fans power OFF and the LCD goes blank (this may take a minute or two), then turn OFF the BATTERY BREAKER (on the SU20KX and SU40KX units, the BATTERY BREAKER is on the back of the UPS; on the SU60KX and SU80KX units, the BATTERY BREAKER is on the back of the battery cabinet).

Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.

 

 

10

1

A

11

3

 

5

4

12

Q4

Q3

Q2

Q1

Output

Manual

Bypass

Main

13

2

Bypass

Input

Input

14

27

Image 27
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesImportant Safety Instructions Location WarningsConnection Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Cabinet Installation PreparationUnpacking Rear of the UPS system PlacementShipping container. Warning The UPS system could tip if it Rear, not from the sidesSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring AC Input/Output Wiring Single UPS Failure to observe proper phase will damage the UPS systemCreate a risk of personal injury and property damage Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input Source10 8-4 Manual Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS Auto Bypass Mode Single UPSOnline Mode Parallel UPS Battery Backup Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSStart-Up, Shutdown and Bypass Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display and Configuration Control Panel DiagramDisplay Hierarchy Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel Setup Parallel GroupParallel ID Control & Test Setup Battery Auto TestBuzzer Manual Battery Test Clear Battery Test ResultForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatAdministrator Password User PasswordLanguage Maintenance Firmware VersionStatistics Advance Use or to read the event log, then press toCommunications Communications InterfacesSnmpwebcard Slot Input Dry Contact Interface External Battery Status Input Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Cabinet Temperature InputsDefault Messages Output Dry Contact Interface DetailOptional Messages Hardware Pin Assignment Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Parallel Configuration PortUPS System Technical Specifications Optional Messages SpecificationsStorage Storage and ServiceWarranty Service