Tripp Lite SU40KX, SU80KX, SU20KX owner manual Start-Up Procedure Parallel UPS

Page 29

9 – Start-Up, Shutdown and Bypass (continued)

1

9-8 Start-Up Procedure (Parallel UPS)

1 Connect the parallel configuration cable A to the DB9 parallel configuration port B of each UPS system. Note: Before starting up

the Parallel UPS system, ensure that the “Parallel ID” is different for each UPS and parallel group is set. (See Section 10-5-5for more details.

2 If the UPS systems have external battery cabinets connected, switch on the external battery cabinet circuit breaker switch A of each battery pack. On the SU20KX or SU40KX, turn ON the battery breaker on the back of the UPS.

9-8 Start-Up Procedure (Parallel UPS) (continued)

3 Switch on the bypass input circuit breaker switch Q2 of each UPS system. After a brief initialization process, the LCD screen will show “ON AUTO BYPASS” and the “BYPASS” LED will illuminate.

4 Switch on the main input circuit breaker switch Q1 of each UPS system.

5 Press the ON button A of one of the UPS systems for 3 seconds (until you hear a beep), then release the button. The inverter will activate and synchronize with the bypass source. Press the ON button for the other UPS system for 3 seconds (until you hear a beep), then release the button. When the inverter of each UPS system is operating normally, they will automatically switch from auto bypass (reserve) mode to online (normal) mode at the same time. The “BYPASS” LED will darken and the “NORMAL” LED will illuminate.

6 Check the output voltage of each UPS system. The phase deviation

between each UPS system should be less than 5V. If the phase deviation is within the acceptable range, switch on the output circuit breaker switch Q4 of each UPS system. Note: For more information on checking the output voltage of each UPS system, see Section 10-4.

 

 

 

 

2

 

 

 

B

 

 

B

A

 

3

1

 

 

 

 

 

 

 

 

4

 

A

 

 

 

 

 

 

 

5

2

 

 

 

 

 

 

 

 

6

 

 

Q2

 

7

 

 

 

 

Output

Manual

Bypass

Main

 

3

Bypass

Input

Input

8

 

 

 

 

 

 

 

 

 

 

Q1

9

 

 

 

 

Output

Manual

Bypass

Main

 

4

Bypass

Input

Input

 

 

 

 

10

 

 

 

A

 

 

 

 

 

 

 

 

11

5

 

 

 

12

 

 

 

 

Q4

 

 

 

 

 

 

 

 

13

Output

Manual

Bypass

Main

 

6

Bypass

Input

Input

 

 

 

 

 

 

 

 

 

14

29

Image 29
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesConnection Warnings Important Safety InstructionsLocation Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Shipping container. Warning The UPS system could tip if it PlacementRear, not from the sides Rear of the UPS systemSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input SourceBattery Backup Mode Single UPS Online Normal Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSPreliminary Checklist Single UPS Control Panel and Breaker DiagramsStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Advance Use or to read the event log, then press toSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces Auxiliary Dry Contact Input Circuit Diagram Remote Emergency Power Off EPO Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputOptional Messages Default MessagesOutput Dry Contact Interface Detail 11-10 RS-232 Serial Port Circuit Diagram Output Dry Contact Circuit DiagramParallel Configuration Port Hardware Pin AssignmentUPS System Technical Specifications Optional Messages SpecificationsWarranty Storage and ServiceService Storage