10-5-4 Charger Setup

Use “

” or ” ” to select “CHARGER”, then press ” ” to confirm.

 

 

 

From the “CHARGER CURRENT” screen, use the scroll buttons

 

 

1

 

 

(

, ) to select the desired setting and press the enter button

 

 

(

) to confirm the setting. Note: The default charger current

 

 

 

setting is 7A.

 

 

 

Each internal power module has a 5 amp charger. Charger current

 

 

 

can be set from a minimum of 2 amps total to a maximum of 5

 

 

 

amps per internal power module, multiplied by the number of

 

 

 

modules. For example, the SU60KX has three internal power

 

 

 

modules, so its charger current range is 2-15 amps. Set the

 

 

 

charger current value based on the size of the battery system. See

 

 

 

Section 10-5-3for more information about determining the size

 

 

 

of the battery system.

 

 

 

Warning: Setting the charger current too high may damage

 

 

 

batteries and reduce their operational lifespan. Consult the

 

 

 

factory for guidance before changing the default setting.

 

 

1

 

 

 

 

2Press “” or ”” to change the charging current, then press ” ” to confirm.

Press “ESC” to return to the “UPS SETUP” menu.

2

46

Image 46
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionLocation Warnings Important Safety InstructionsConnection Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Preparation Cabinet InstallationUnpacking Rear, not from the sides PlacementShipping container. Warning The UPS system could tip if it Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring Failure to observe proper phase will damage the UPS system AC Input/Output Wiring Single UPSCreate a risk of personal injury and property damage AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsAuto Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSBattery Backup Mode Parallel UPS Online Mode Parallel UPSAuto Bypass Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSStandard Start-Up Procedure Single UPS Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Control Panel Diagram Display and ConfigurationDisplay Hierarchy Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel Group Parallel SetupParallel ID Battery Auto Test Control & Test SetupBuzzer Clear Battery Test Result Manual Battery TestForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastUser Password Administrator PasswordLanguage Firmware Version MaintenanceStatistics Use or to read the event log, then press to AdvanceCommunications Interfaces CommunicationsSnmpwebcard Slot Input Dry Contact Interface External Battery Cabinet Temperature Inputs Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Status InputOutput Dry Contact Interface Detail Default MessagesOptional Messages Parallel Configuration Port Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesService Storage and ServiceWarranty Storage