Tripp Lite SU40KX, SU80KX, SU20KX owner manual For more information about the Snmpwebcard accessory

Page 8

14 – Front and Rear Panel Features (continued)

J

2

3

L M K N

4

5

6

O

P

H

H

I

I

SU40KX shown (rear)

7

8

9

10

11

12

13

14

Note: Individual models may vary from diagrams. Unit shown with front bezels removed.

H

Levelers: The levelers provide long-term support for the UPS system.

 

Casters: The casters are designed for small position adjustments within the final installation location only; they are not designed for moving

I

 

the UPS system over longer distances. The casters are not designed to provide long-term support for the UPS system after final installation.

 

Use the levelers to provide long-term support.

 

Accessory Slot: Remove the cover panel to install a Tripp Lite SNMPWEBCARD accessory. The SNMPWEBCARD accessory provides an

J

 

Ethernet interface for the UPS system and enables remote monitoring and control via SNMP, Web browser or telnet. Visit www.tripplite.com

 

for more information about the SNMPWEBCARD accessory.

 

RS-232 Serial Communications Port: This DB9 port connects the UPS system to compatible workstations or servers, enabling automatic

K

 

shutdown during extended blackouts and monitoring of operating and power conditions.

 

 

L

Parallel Configuration Port: This DB9 port connects the UPS system to another UPS system of identical type and capacity for use in a

 

 

parallel redundancy (1+1) configuration. See Section 7 – Wiring and Section 8 – Operating Modes for more information.

 

Input Dry Contact Interface: This interface receives dry contact signals that allow the UPS system to receive commands and monitor

M

 

external battery conditions. See Section 11 - Communications for more information.

 

 

N

Output Dry Contact Interface: This interface allows the UPS system to send information via dry contact communications. See Section 11 –

 

Communications for more information.

 

Internal Battery Circuit Breaker Switch (SU20KX and SU40KX only): Controls the input/output power of the UPS system’s internal

O

 

batteries.

 

 

P

Terminal Block Cover: Remove the terminal block cover to access the UPS system’s input, bypass input, external battery cabinet, output and

 

 

grounding connection terminals. Wiring conduits pass through the circular knockouts in the terminal block cover. See Section 7 – Wiring for

 

more information, including a detailed diagram of the terminal block.

8

Image 8
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionConnection Warnings Important Safety InstructionsLocation Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Placement Shipping container. Warning The UPS system could tip if itRear, not from the sides Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsOnline Normal Mode Single UPS Battery Backup Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSControl Panel and Breaker Diagrams Preliminary Checklist Single UPSStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Use or to read the event log, then press to AdvanceSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces Remote Emergency Power Off EPO Circuit Diagram Auxiliary Dry Contact Input Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputOptional Messages Default MessagesOutput Dry Contact Interface Detail Output Dry Contact Circuit Diagram 11-10 RS-232 Serial Port Circuit DiagramParallel Configuration Port Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesStorage and Service WarrantyService Storage