11 – Communications (continued)

1

11-8 Output Dry Contact Interface Detail

The UPS system has six dry contact output connections. These contacts can be normally open or normally closed.

 

 

Default Messages

 

 

 

Contact

Message

Description

Pin 1-2

Load on inverter

The UPS system is working normally.

 

 

 

Pin 3-4

Load on auto bypass

The UPS system is in bypass mode.

 

 

 

Pin 5-6

Mains input failure with load on inverter

Utility power is absent (blackout) or abnormal. The UPS system is in battery backup mode.

 

 

 

Pin 7-8

Battery low

The UPS system is in battery backup mode, and battery voltage is lower than 220V.

 

 

 

Pin 9-10

Bypass input abnormal

The bypass input is abnormal (frequency / phase).

 

 

 

Pin 11-12

Battery test failure

The battery voltage is lower than the reference value.

 

 

 

2

3

4

 

Optional Messages

 

 

Message

Description

Internal communication failure

Communication with one of the internal components is not normal.

 

 

External parallel communication failure

In a parallel redundancy installation, the parallel communication is not normal.

 

 

Output overload warning/shutdown

The load exceeds the capacity of the UPS system.

 

 

Power module fault shutdown

The UPS system has shut down due to an internal power module failure.

 

 

Power module warning

An internal power module has an error, but the UPS system can still function normally.

 

 

EPO activated

The UPS system’s output is disabled by the emergency power off (EPO) function.

 

 

Load on manual bypass

The UPS system is in manual bypass mode.

 

 

Battery cabinet over temperature warning/shutdown

The temperature of the external battery cabinet is too high.

 

 

Output voltage abnormal

The UPS system’s output voltage is too high or too low.

 

 

Battery need replace

According to the data in the “BAT DATE SETTING”, the UPS system is overdue for battery

 

replacement. (See Section 10-5-3for more information.)

 

 

Bypass over temperature warning/shutdown

The temperature of the bypass “static transfer switch” is too high.

 

 

Battery ground fault

The battery has a grounding error.

 

 

Bypass static switch fault

The bypass “static transfer switch” is abnormal.

 

 

Note: If you require optional messages to be enabled, contact Tripp Lite.

57

5

6

7

8

9

10

11

12

13

14

Image 57
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesImportant Safety Instructions Location WarningsConnection Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Cabinet Installation PreparationUnpacking Shipping container. Warning The UPS system could tip if it PlacementRear, not from the sides Rear of the UPS systemSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring AC Input/Output Wiring Single UPS Failure to observe proper phase will damage the UPS systemCreate a risk of personal injury and property damage Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input SourceBattery Backup Mode Single UPS Online Normal Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSOnline Mode Parallel UPS Battery Backup Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSPreliminary Checklist Single UPS Control Panel and Breaker DiagramsStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display and Configuration Control Panel DiagramDisplay Hierarchy Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel Setup Parallel GroupParallel ID Control & Test Setup Battery Auto TestBuzzer Manual Battery Test Clear Battery Test ResultForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatAdministrator Password User PasswordLanguage Maintenance Firmware VersionStatistics Advance Use or to read the event log, then press toCommunications Communications InterfacesSnmpwebcard Slot Input Dry Contact Interface Auxiliary Dry Contact Input Circuit Diagram Remote Emergency Power Off EPO Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputDefault Messages Output Dry Contact Interface DetailOptional Messages 11-10 RS-232 Serial Port Circuit Diagram Output Dry Contact Circuit DiagramParallel Configuration Port Hardware Pin AssignmentUPS System Technical Specifications Optional Messages SpecificationsWarranty Storage and ServiceService Storage