Tripp Lite SU20KX, SU80KX, SU40KX owner manual External Battery Cabinet Wiring

Page 19

7 – Wiring (continued)

7-6 External Battery Cabinet Wiring

Warning: External battery cabinets vary. Read the external battery cabinet’s documentation before attempting to connect it to the UPS system. Use only external battery cabinets that have been approved by Tripp Lite.

Note: An external battery cabinet is required with models SU60KX and SU80KX. It is optional with models SU20KX and SU40KX. Contact Tripp Lite for external battery cabinet ordering information.

1 De-energize all input and output (AC and DC) of the UPS system

 

and external battery cabinet, and confirm that the external battery

 

cabinet breaker switch A is off. (If the UPS system has already

 

been wired to an AC power source, see Section 9-6for shutdown

A

instructions.)

 

1

1

2

3

4

5

2 Remove the terminal block covers from the UPS system and external battery cabinet.

3 Connect the positive (+), neutral (N) and negative (-) UPS system connection terminals of the external battery cabinet to the corresponding positive (+), neutral (N) and negative (-) external battery connection terminals of the UPS system. See Section 7-3and the external battery cabinet’s documentation for terminal block diagrams. See Section 7-4for wiring diagrams. See Section 7-5for cable size requirements. Cabling should be protected by flexible conduit and routed through the appropriate knockouts in the terminal block cover. Warning: Observe proper polarity by connecting negative to negative and positive to positive. Failure to observe proper polarity will damage the UPS system and create a risk of personal injury and property damage.

4 Connect the external battery cabinet’s grounding terminal A to the UPS system’s corresponding grounding terminal B with a 4 AWG (5.189 mm) ground cable. Keep the ground cable connected at all times after installation.

5 Connect the UPS system’s grounding terminal A to your facility’s earth ground B with a 4 AWG (5.189 mm) minimum ground cable. Keep the ground cable connected at all times after installation.

6 Replace the terminal block cover of the external battery cabinet. If you do not plan to wire the AC input/output of the UPS system at this time, replace the terminal block cover of the UPS system.

B

A

5

19

2

+

3

A

4

6

+

B

6

7

8

9

10

11

12

13

14

Image 19
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesLocation Warnings Important Safety InstructionsConnection Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Preparation Cabinet InstallationUnpacking Rear of the UPS system PlacementShipping container. Warning The UPS system could tip if it Rear, not from the sidesSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring Failure to observe proper phase will damage the UPS system AC Input/Output Wiring Single UPSCreate a risk of personal injury and property damage Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input Source10 8-4 Manual Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS Auto Bypass Mode Single UPSBattery Backup Mode Parallel UPS Online Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSStart-Up, Shutdown and Bypass Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Control Panel Diagram Display and ConfigurationDisplay Hierarchy Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel Group Parallel SetupParallel ID Battery Auto Test Control & Test SetupBuzzer Clear Battery Test Result Manual Battery TestForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatUser Password Administrator PasswordLanguage Firmware Version MaintenanceStatistics Advance Use or to read the event log, then press toCommunications Interfaces CommunicationsSnmpwebcard Slot Input Dry Contact Interface External Battery Status Input Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Cabinet Temperature InputsOutput Dry Contact Interface Detail Default MessagesOptional Messages Hardware Pin Assignment Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Parallel Configuration PortUPS System Technical Specifications Optional Messages SpecificationsStorage Storage and ServiceWarranty Service