Tripp Lite SU80KX, SU20KX, SU40KX owner manual Shutdown Procedure Parallel UPS

Page 30

19 – Start-Up, Shutdown and Bypass (continued)

 

9-9 Shutdown Procedure (Parallel UPS)

2

Warning: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm that all loads

are turned off or place the UPS systems in manual bypass mode to keep loads powered by the bypass (reserve) power source.

3

4

5

6

7

8

9

10

1 For the UPS system you wish to shut down, press the OFF button

Afor 3 seconds (until you hear a beep), then release the button. If the other UPS system can support the connected equipment loads alone, the UPS system that was turned off will shut down its inverter and its LCD screen will read “LOAD NOT POWERED”. The other UPS system’s LCD screen will read “ONLINE MODE”. If the total connected equipment load is too large to be handled by a single UPS system, both UPS systems will shut down their inverters and switch to bypass mode, and their LCD screens will read “ON AUTO BYPASS”.

2 For the UPS system you wish to shut down, switch off the main input circuit breaker switch Q1 , then switch off the output circuit breaker switch Q4 .

3 For the UPS system you wish to shut down, switch off the bypass input circuit breaker switch Q2 .

4 When the UPS system is completely shut down, the LCD screen will be completely off. If the UPS systems have external battery cabinets connected, switch off the external battery cabinet circuit breaker switch A of each battery pack. On the SU20KX or SU40KX, turn OFF the battery breaker on the back of the UPS.

Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure

to recharge the batteries periodically may cause irreversible battery damage.

1

A

 

Q4

 

 

Q1

Output

Manual

Bypass

Main

2

Bypass

Input

Input

 

 

 

Q2

Output

Manual

Bypass

Main

3

Bypass

Input

Input

 

 

 

 

A

 

 

4

 

 

 

11

12

13

14

30

Image 30
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionImportant Safety Instructions Location WarningsConnection Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Cabinet Installation PreparationUnpacking Rear, not from the sides PlacementShipping container. Warning The UPS system could tip if it Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring AC Input/Output Wiring Single UPS Failure to observe proper phase will damage the UPS systemCreate a risk of personal injury and property damage AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsAuto Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSOnline Mode Parallel UPS Battery Backup Mode Parallel UPSAuto Bypass Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSStandard Start-Up Procedure Single UPS Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display and Configuration Control Panel DiagramDisplay Hierarchy Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel Setup Parallel GroupParallel ID Control & Test Setup Battery Auto TestBuzzer Manual Battery Test Clear Battery Test ResultForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastAdministrator Password User PasswordLanguage Maintenance Firmware VersionStatistics Use or to read the event log, then press to AdvanceCommunications Communications InterfacesSnmpwebcard Slot Input Dry Contact Interface External Battery Cabinet Temperature Inputs Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Status InputDefault Messages Output Dry Contact Interface DetailOptional Messages Parallel Configuration Port Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesService Storage and ServiceWarranty Storage