Tripp Lite SU40KX, SU80KX, SU20KX owner manual AC Input/Output Wiring Single UPS

Page 20

17 – Wiring (continued)

7-7 AC Input/Output Wiring (Single UPS)

1 After de-energizing all input and output (AC and DC) of the UPS 2 system, remove the terminal block cover from the UPS system.

3

4 2 If you did not connect the ground cable in Section 7-6, connect the UPS system’s grounding terminal A to your facility’s earth ground

Bwith a 4 AWG (5.189 mm) ground cable. Keep the ground cable connected at all times after installation.

5

6

 

 

3

Remove the UPS system’s front bezel to expose the circuit

 

 

 

 

breakers. First, confirm that the main input circuit breaker switch

7

 

 

 

Q1

and the bypass input circuit breaker switch

Q2

are both off.

 

 

 

Second, confirm that the manual bypass circuit breaker switch

 

 

 

 

 

Q3

 

 

 

 

is off. Third, confirm that the output circuit breaker switch

 

is

 

 

 

 

Q4

 

 

 

 

off.

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Confirm the phase of each cable, then connect the cables according

 

 

 

 

 

4

9

 

 

 

to the UPS system terminal block diagram in Section 7-3. See

 

 

 

Section 7-5for cable size requirements. Cabling should be

 

 

 

 

protected by flexible conduit and routed through the appropriate

 

 

 

 

knockouts in the terminal block cover. Warning: Observe proper

 

 

 

 

 

phase rotation by connecting R to R, S to S, T to T and N to N.

10

 

 

 

Failure to observe proper phase will damage the UPS system

 

 

 

and create a risk of personal injury and property damage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

Replace the UPS system’s terminal block cover.

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

B

A

2

Q4

 

Q3

 

Q2

 

Q1

 

 

 

 

 

 

 

 

 

 

 

3

 

R S T N R S T N

R S T N

4

 

5

20

Image 20
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionConnection Warnings Important Safety InstructionsLocation Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Placement Shipping container. Warning The UPS system could tip if itRear, not from the sides Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsOnline Normal Mode Single UPS Battery Backup Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSControl Panel and Breaker Diagrams Preliminary Checklist Single UPSStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Use or to read the event log, then press to AdvanceSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces Remote Emergency Power Off EPO Circuit Diagram Auxiliary Dry Contact Input Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputOptional Messages Default MessagesOutput Dry Contact Interface Detail Output Dry Contact Circuit Diagram 11-10 RS-232 Serial Port Circuit DiagramParallel Configuration Port Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesStorage and Service WarrantyService Storage