Tripp Lite SU40KX, SU80KX, SU20KX Switching from Manual Bypass to Normal Mode Parallel UPS

Page 32

19 – Start-Up, Shutdown and Bypass (continued)

9-11 Switching from Manual Bypass to Normal Mode (Parallel UPS)

2

1

If the UPS systems have external battery cabinets connected,

 

switch off the external battery cabinet circuit breaker switch A

 

 

of each battery pack. On the SU20KX or SU40KX, turn OFF the

 

 

battery breaker on the back of the UPS.

 

3

 

 

 

 

 

4

2

Switch on the bypass input circuit breaker switch Q2 and the

 

output circuit breaker switch

Q4 of each UPS system.

5

 

 

 

 

 

 

3 Confirm that both UPS systems are shut down, then switch off

 

 

the manual bypass input circuit breaker switch Q3 of each UPS

 

 

system. The LCD screen will read “ON AUTO BYPASS”.

6

4

Switch on the main input circuit breaker switch Q1 of each UPS

 

 

system.

 

 

 

 

5

Press the ON button A of the first UPS systems for 3 seconds

 

 

(until you hear a beep), then release the button. Press the ON

7

 

button for the second UPS system for 3 seconds (until you hear

 

a beep), then release the button. When the inverter of each UPS

 

 

system is operating normally, they will switch to online (normal)

 

 

mode at the same time.

 

 

8

 

 

 

 

 

 

 

 

 

 

Q1

9

 

 

 

 

 

 

 

Output

Manual

Bypass

Main

 

4

 

Bypass

Input

Input

 

 

 

 

 

A

1

 

 

 

Q4

 

Q2

 

Output

Manual

Bypass

Main

2

Bypass

Input

Input

 

 

 

 

Q3

 

 

Output

Manual

Bypass

Main

3

Bypass

Input

Input

 

 

 

 

 

 

A

5

10

11

12

13

14

32

Image 32
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionConnection Warnings Important Safety InstructionsLocation Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Placement Shipping container. Warning The UPS system could tip if itRear, not from the sides Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsOnline Normal Mode Single UPS Battery Backup Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSControl Panel and Breaker Diagrams Preliminary Checklist Single UPSStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Use or to read the event log, then press to AdvanceSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces Remote Emergency Power Off EPO Circuit Diagram Auxiliary Dry Contact Input Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputOptional Messages Default MessagesOutput Dry Contact Interface Detail Output Dry Contact Circuit Diagram 11-10 RS-232 Serial Port Circuit DiagramParallel Configuration Port Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesStorage and Service WarrantyService Storage