Tripp Lite SU40KX, SU80KX, SU20KX UPS System Technical Specifications Optional Messages

Page 59

12 – Specifications

1

12-1 UPS System Technical Specifications

Optional Messages

 

 

 

 

Model

 

SU20KX

 

SU40KX

 

SU60KX

 

SU80KX

 

 

 

 

(Capacity)

(20kVA/16kW)

 

(40kVA/32kW)

 

(60kVA/48kW)

 

(80kVA/64kW)

 

Input

Input Voltage

 

 

220/380V, 230/400V or 240/415V AC, 3O, 4-wire + ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Regulation

 

 

-25% / +20%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Harmonic Distortion

 

 

< 4% (Full Load)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PFC (Full Load)

 

 

> 0.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

 

 

50 / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Tolerance

 

 

45 ~ 65 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Output Voltage

 

 

220/380V, 230/400V or 240/415V AC, 3O, 4-wire + ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Frequency

 

 

50 / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Harmonic (Linear Load)

3%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Regulation

Static

±1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dynamic

±7% (10% ~ 90% Linear Load)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Regulation

Interior Oscillator

±0.05 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Synchronized

±5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload

 

 

125% : 10 minutes; 150% : 1 minute

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Audible Warning

Battery Backup

 

 

Intermittent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Abnormal

 

 

Continuous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

LED

 

 

UPS Status: Normal • Bypass • Backup • Fault

 

 

 

 

 

 

 

 

 

 

 

 

LCD

 

 

Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage

 

 

 

 

 

UPS abnormal messages with intelligent self-diagnosis.

 

 

 

 

 

 

 

 

 

 

 

 

 

Interface

Standard

 

 

RS-232, Dry Contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional

 

 

SNMPWEBCARD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Others

Parallel Redundancy

 

 

Yes (1+1 for 2 UPS systems of the same type and capacity only.)

 

 

 

 

 

 

 

 

 

 

 

 

 

EPO

 

 

Standard (Local and Remote)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SRAM Event Log

 

 

500 Records

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Configuration

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot Standby Installation

 

 

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Temperature Compensation

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Cold-Start

 

 

Standard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overall

Efficiency

Normal

94%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECO

97%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer Time

 

 

0 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

 

32° F ~ 104° F (0° C ~ 40° C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity (non-condensing)

90%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noise (1 m)

 

 

 

65 dBA

 

68 dBA

 

70 dBA

 

70 dBA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions (Power Module)

Width

520 mm (20.47 in)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

850 mm (33.46 in)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

1165 mm (45.86 in)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight (Power Module)

 

 

267 kg (589 lb*)

 

412 kg (908 lb*)

 

210 kg (463 lb)

 

244 kg (538 lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* With internal batteries.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12-2 UPS System Floor Loading Table

 

12-3 Battery Pack Floor Loading Table

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

4

5

6

7

8

9

10

11

12

13

Model

SU20KX

SU40KX

SU60KX

SU80KX

 

 

BP480V26B

BP480V40C

 

 

Weight

267 kg

412 kg

210 kg

244 kg

 

 

(40 12V batteries;

(40 12V batteries;

 

 

 

Model

26AH each)

40AH each)

 

 

 

 

 

 

 

 

 

 

Floor Loading

600 kg/m2

927 kg/m2

475 kg/m2

552 kg/m2

 

Weight

470 kg (1036 lb)

700 kg (1543 lb)

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor Loading

1064 kg/m2

1575 kg/m2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 59
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesConnection Warnings Important Safety InstructionsLocation Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Rear of the UPS system PlacementShipping container. Warning The UPS system could tip if it Rear, not from the sidesSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input Source10 8-4 Manual Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS Auto Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSStart-Up, Shutdown and Bypass Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Advance Use or to read the event log, then press toSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces External Battery Status Input Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Cabinet Temperature InputsOptional Messages Default MessagesOutput Dry Contact Interface Detail Hardware Pin Assignment Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Parallel Configuration PortUPS System Technical Specifications Optional Messages SpecificationsStorage Storage and ServiceWarranty Service