Tripp Lite SU20KX, SU80KX, SU40KX owner manual Preliminary Checklist Parallel UPS

Page 28

19 – Start-Up, Shutdown and Bypass (continued)

2

3

9-6 Shutdown Procedure (Single UPS) (continued)

 

 

 

 

To transfer the critical load to NORMAL mode from Manual

 

 

 

 

Bypass:

 

 

 

 

11.

Confirm the UPS is in MANUAL BYPASS (the MANUAL

 

 

 

 

 

BYPASS circuit breaker Q3 is ON; the OUTPUT Q4 , BYPASS

Q4

Q3

Q2

Q1

 

INPUT Q2 and MAIN INPUT Q1 circuit breakers are OFF).

 

 

 

 

22. Turn ON the BATTERY BREAKER (on the SU20KX and

 

 

 

 

 

SU40KX units, the BATTERY BREAKER is on the back of

Output

Manual

Bypass

Main

 

the UPS; on the SU60KX and SU80KX units, the BATTERY

 

1

Bypass

Input

Input

 

BREAKER is on the back of the battery cabinet).

 

 

 

 

 

 

 

 

4

5

6

7

8

33. Turn ON the BYPASS INPUT circuit breaker Q2 (the amber Bypass LED should come on and the LCD will display “Load Unprotected-On Manual Bypass).

44. Confirm the amber BYPASS LED is ON. Do not proceed if it is not ON.

55. Turn ON the OUTPUT circuit breaker Q4 .

66. Turn OFF the MANUAL BYPASS circuit breaker Q3 . The LCD will display “Load Unprotected-On Auto Bypass”.

77. Turn ON the MAIN INPUT circuit breaker Q1 . The Power Module fans will turn ON.

88. Press and hold the green ON button until the UPS beeps, then release the button. The UPS will perform a self-test diagnostic and the LCD will display “Self Diagnosis”. After the UPS self-test is completed, the UPS will transfer to NORMAL mode (green LED ON and LCD displays “Load Protected-On Line Mode”).

99. Confirm there are no active alarms present (“!” on the display and audible beeping). If an alarm is present, press the UP or DOWN arrows to display the active alarm. Correct the action as required.

10Scroll through the Measure Menu and confirm all input and output power readings are within the recommended specifications.

Q2

3

Q3

6

Q4

5

Q1

7

11If any problems are noted, contact your technical support personnel

9

for further assistance.

12 The critical load is now supported by conditioned battery back-up

power.

10

11

12

13

14

9-7 Preliminary Checklist (Parallel UPS)

Warning: Parallel configuration requires exactly two UPS systems (1+1 redundancy or capacity). Do not attempt to link more than two UPS systems via parallel configuration. The UPS systems must have the same rating and capacity for parallel UPS installation. Attempting to link dissimilar UPS systems will damage the UPS systems and create a serious risk of personal injury and property damage.

All circuit breaker switches should be off, including the breakers of the external battery cabinets.

Confirm that no voltage potential exists between Neutral and Ground.

Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS systems.

Each UPS must have a different “Parallel ID”that indicates the UPS systems are being run in parallel. See Section 10-5-5for more details.

Note: After start-up, the UPS systems will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS systems will provide AC power to the connected equipment load.

28

Image 28
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionLocation Warnings Important Safety InstructionsConnection Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Preparation Cabinet InstallationUnpacking Placement Shipping container. Warning The UPS system could tip if itRear, not from the sides Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring Failure to observe proper phase will damage the UPS system AC Input/Output Wiring Single UPSCreate a risk of personal injury and property damage AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsOnline Normal Mode Single UPS Battery Backup Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSBattery Backup Mode Parallel UPS Online Mode Parallel UPSAuto Bypass Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSControl Panel and Breaker Diagrams Preliminary Checklist Single UPSStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Control Panel Diagram Display and ConfigurationDisplay Hierarchy Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel Group Parallel SetupParallel ID Battery Auto Test Control & Test SetupBuzzer Clear Battery Test Result Manual Battery TestForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastUser Password Administrator PasswordLanguage Firmware Version MaintenanceStatistics Use or to read the event log, then press to AdvanceCommunications Interfaces CommunicationsSnmpwebcard Slot Input Dry Contact Interface Remote Emergency Power Off EPO Circuit Diagram Auxiliary Dry Contact Input Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputOutput Dry Contact Interface Detail Default MessagesOptional Messages Output Dry Contact Circuit Diagram 11-10 RS-232 Serial Port Circuit DiagramParallel Configuration Port Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesStorage and Service WarrantyService Storage