16 – Internal Battery Connection (continued)

6-2 Internal Battery Connection Procedure (continued)

6 Slide a battery string with a red cable into an empty slot within 2 the battery compartment. Make sure the battery string is oriented

as shown in the diagram. Note: Start with the empty slots at the bottom of the battery compartment and work toward the empty slots at the top of the battery compartment.

3

4

7 Slide a battery string with a black cable into an empty slot within the battery compartment, next to the battery string that you inserted

5 in step 6. Make sure the battery string is oriented as shown in the diagram. Repeat steps 6 and 7 as needed until all the battery strings have been inserted into the empty battery slots. Note: Depending on the model of the UPS system, some battery compartment slots

TERMINALS

SIDE VIEW

6

TERMINALS

6

7

may remain empty.

SIDE VIEW

7

8 Reconnect the fuse block bracket. (The letters on the fuse block bracket should be upright when it is in the correct orientation.)

8

9

8

 

 

 

 

Connect the blue and white jumper cables on each internal battery

10

 

9

 

 

 

pack to the corresponding fuse block. The labeling next to the fuse

 

 

 

 

block identifies the correct fuse block for each cable.

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

Insert the battery cartridge fuses into each fuse block. The fuses are

 

10

 

 

 

 

interchangeable. Make sure the fuses are firmly snapped into place.

 

 

 

 

Warning: Battery cartridge fuses must be inserted last due to

 

 

 

 

 

 

 

 

potential arcing of connectors. Blown fuses must be replaced

13

 

 

 

by a qualified electrician. Replace only with fuses of the same

 

 

 

type and rating.

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

9

10

14

Image 14
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionConnection Warnings Important Safety InstructionsLocation Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Rear, not from the sides PlacementShipping container. Warning The UPS system could tip if it Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsAuto Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSStandard Start-Up Procedure Single UPS Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Use or to read the event log, then press to AdvanceSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces External Battery Cabinet Temperature Inputs Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Status InputOptional Messages Default MessagesOutput Dry Contact Interface Detail Parallel Configuration Port Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesService Storage and ServiceWarranty Storage