Tripp Lite SU20KX Communications Interfaces, Snmpwebcard Slot Input Dry Contact Interface

Page 55

11 – Communications

1

Note: The communications connections described in this section are optional. The UPS system will function properly without these connections.

11-1 Communications Interfaces

2

SNMPWEBCARD Slot

3

4

5

Input Dry Contact

Interface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parallel

 

 

 

Output

 

Dry

 

RS-232

Configuration Port

 

 

 

 

 

Serial Port

 

Contact Interface

 

 

 

 

 

 

 

Note: The following connectors are provided with the UPS: P1, P2 and a 12 position strip for the output dry contacts. P3 and P7 are only shipped with the optional BP480V26B or BP480V40C matching battery cabinet.

11-2 SNMPWEBCARD Slot

Remove the cover panel to install a Tripp Lite SNMPWEBCARD accessory. The SNMPWEBCARD accessory provides an Ethernet interface for the UPS system and enables remote monitoring and control via SNMP, Web browser or telnet. Visit www.tripplite.com for more information about ordering the SNMPWEBCARD accessory.

11-3 Input Dry Contact Interface

The input dry contact interface receives contact-closure signals that allow the UPS system to receive commands and monitor external battery conditions:

P1—Remote Emergency Power Off (EPO) (See Section 11-4.)

P2—Auxiliary Dry Contact Inputs (2 sets) (Input Contact A: Pin 1,2 Rated for 12V DC minimum 0.1A (nominal); Input Contact B: Pin 3,4 Rated for 12V DC minimum 0.1A (nominal). See Section 11-5.)

P3—External Battery Cabinet Temperature 1 (Temperature Sensor Inputs from external battery cabinets. See Section 11-6.) P4—External Battery Cabinet Temperature 2 (Temperature Sensor Inputs from external battery cabinets. See Section 11-6.) P5—External Battery Cabinet Temperature 3 (Temperature Sensor Inputs from external battery cabinets. See Section 11-6.) P6—External Battery Cabinet Temperature 4 (Temperature Sensor Inputs from external battery cabinets. See Section 11-6.)

P7—External Battery Status (For use with battery status cable supplied with external battery cabinets-BP480V26B or BP480V40C.)

Note: Do not apply voltages to the REPO contacts or auxiliary dry contacts. Damage to the UPS may result. For the REPO, the switch must be latching in order to keep output power OFF from the UPS output.

55

6

7

8

9

10

11

12

13

14

Image 55
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesLocation Warnings Important Safety InstructionsConnection Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Preparation Cabinet InstallationUnpacking Rear of the UPS system PlacementShipping container. Warning The UPS system could tip if it Rear, not from the sidesSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring Failure to observe proper phase will damage the UPS system AC Input/Output Wiring Single UPSCreate a risk of personal injury and property damage Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input Source10 8-4 Manual Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS Auto Bypass Mode Single UPSBattery Backup Mode Parallel UPS Online Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSStart-Up, Shutdown and Bypass Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Control Panel Diagram Display and ConfigurationDisplay Hierarchy Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel Group Parallel SetupParallel ID Battery Auto Test Control & Test SetupBuzzer Clear Battery Test Result Manual Battery TestForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatUser Password Administrator PasswordLanguage Firmware Version MaintenanceStatistics Advance Use or to read the event log, then press toCommunications Interfaces CommunicationsSnmpwebcard Slot Input Dry Contact Interface External Battery Status Input Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Cabinet Temperature InputsOutput Dry Contact Interface Detail Default MessagesOptional Messages Hardware Pin Assignment Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Parallel Configuration PortUPS System Technical Specifications Optional Messages SpecificationsStorage Storage and ServiceWarranty Service