Tripp Lite SU80KX, SU20KX, SU40KX owner manual Control Panel Features

Page 6

13 – Control Panel Features

D

 

C

 

B

 

A

 

E

 

F

 

G

 

H

 

I

 

J

 

K

2

3

4

A

5 B

C

6 D

E

7

F

G

8 H

I

J

9

10

K

“NORMAL” LED: This green light illuminates to indicate that the UPS system is in online (normal) mode. The primary AC input supply is present and within standard operating parameters.

“BATTERY” LED: This amber light illuminates when the UPS system is in battery backup mode, discharging the batteries to provide power to connected equipment. An audible alarm will also sound.

“BYPASS” LED: This amber light illuminates when the UPS system is in bypass mode (auto bypass or manual bypass). Battery backup power will not be available to connected equipment while the UPS system is in bypass mode, but connected equipment loads will be supported by the bypass (reserve) power source.

“FAULT” LED: This red light illuminates when any UPS system or input power fault occurs. Available diagnostic information will be displayed on the LCD screen.

LCD Status Screen: This illuminated LCD status screen displays text and graphics to indicate a wide range of UPS system operating

conditions and diagnostic data. Note: The LCD backlight will turn off after 10 minutes of inactivity. Turn on the backlight by momentarily pressing the ON button or one of the scroll buttons.

“ESC” (Escape) Button: Press this button to return to the previous page or menu.

Scroll Buttons ( and ): Press these buttons to move the cursor up or down and navigate the control panel menus and screens. These buttons are also used for data entry in several screens.

Enter Button ( ): Press this button to select a menu item or confirm a setting change.

ON Button: Press and hold this button for 3 seconds to turn the UPS system’s inverter ON.

OFF Button: Press and hold this button for 3 seconds to turn the UPS system’s inverter OFF. If the UPS system is in online (normal) mode, it will switch to auto bypass mode.

Note: Switching the inverter OFF does not stop the converter stage of the UPS and therefore, the connected battery is still charging as required.

Note: After switching the inverter OFF, if the battery circuit breaker or AC main input circuit breaker are opened and remain open for an extended period of time, the batteries should be recharged periodically. At a minimum, the batteries should be charged for an uninterrupted 24-hour period every 3 months to maintain their longest usable life. Failure to recharge the batteries may cause irreversible battery damage.

“EPO” (Emergency Power Off) Button: Press this button to turn the UPS system’s output OFF and also disable bypass output. If the UPS system is in battery backup mode when the EPO button is activated:

Main output and bypass output are turned off, the alarm sounds, fans shut down after approximately one minute, and control circuitry

11

remains active.

12

13

14

Releasing the EPO button (by pressing it again) turns off the UPS system completely, including the alarm and control circuit. Press the ON button for 3 seconds to restart the UPS system.

If the UPS system is in online (normal) mode when the EPO button is activated:

Main output and bypass output are turned off, the alarm sounds, fans and control circuitry remain active.

Releasing the EPO button (by pressing it again) turns off the alarm and places the UPS system in auto bypass mode. Press the ON button for 3 seconds to return the UPS system to online (normal) mode.

See Section 10 – Display and Configuration for detailed information about the control panel’s menus and displays.

6

Image 6
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionImportant Safety Instructions Location WarningsConnection Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Cabinet Installation PreparationUnpacking Rear, not from the sides PlacementShipping container. Warning The UPS system could tip if it Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring AC Input/Output Wiring Single UPS Failure to observe proper phase will damage the UPS systemCreate a risk of personal injury and property damage AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsAuto Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSOnline Mode Parallel UPS Battery Backup Mode Parallel UPSAuto Bypass Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSStandard Start-Up Procedure Single UPS Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display and Configuration Control Panel DiagramDisplay Hierarchy Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel Setup Parallel GroupParallel ID Control & Test Setup Battery Auto TestBuzzer Manual Battery Test Clear Battery Test ResultForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastAdministrator Password User PasswordLanguage Maintenance Firmware VersionStatistics Use or to read the event log, then press to AdvanceCommunications Communications InterfacesSnmpwebcard Slot Input Dry Contact Interface External Battery Cabinet Temperature Inputs Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Status InputDefault Messages Output Dry Contact Interface DetailOptional Messages Parallel Configuration Port Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesService Storage and ServiceWarranty Storage