10 – Display and Configuration (continued)

10-5-5 Parallel Setup

Use “” or ”” to select “Parallel”, then press ” ” to confirm.

1Use “” or ”” to select the desired item, then press ” ” to confirm.

1

2Parallel Group

The parallel group setting tells the UPS that it is operating in parallel. Group 1 is the default setting. See Section 7 – Wiring for wiring considerations. Note: Possible settings are 1 or 2.

2

3Parallel ID

Identifies the UPS number (1-8) within the group. When paralleling UPS systems, each must have a unique Parallel ID.

Press “ESC” to return to the “UPS SETUP” menu.

3

47

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Image 47
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesConnection Warnings Important Safety InstructionsLocation Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Rear of the UPS system PlacementShipping container. Warning The UPS system could tip if it Rear, not from the sidesSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input Source10 8-4 Manual Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS Auto Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSStart-Up, Shutdown and Bypass Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Advance Use or to read the event log, then press toSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces External Battery Status Input Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Cabinet Temperature InputsOptional Messages Default MessagesOutput Dry Contact Interface Detail Hardware Pin Assignment Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Parallel Configuration PortUPS System Technical Specifications Optional Messages SpecificationsStorage Storage and ServiceWarranty Service