Tripp Lite SU80KX AC Input/Output Wiring Parallel UPS Single Input Source, Parallel UPS Warnings

Page 21

7 – Wiring (continued)

1

 

7-8 AC Input/Output Wiring (Parallel UPS – Single Input Source)

 

Parallel UPS Warnings:

2

• The total input cable length must be equal to the total

 

output cable length in order to prevent unbalanced load

 

sharing between two UPS systems under reserve mode

 

(i.e. Res1 + OP1 = Res2 + OP2; deviation must be <10%).

 

• Parallel configuration only supports 2 UPS systems (1+1

3

redundancy or capacity). Do not attempt to link more than

 

two UPS systems via parallel configuration.

 

• The UPS systems must have the same rating and capacity

 

for parallel UPS installation. Attempting to link

4

dissimilar UPS systems will damage the UPS systems

 

and create a serious risk of personal injury and property

 

damage.

 

 

• Each UPS must have its Parallel group set to 2 and a

 

 

 

5

 

different “Parallel ID” that indicates the UPS systems are

1

 

 

 

being run in parallel. (See Section 10-5-5for more details.)

 

 

 

 

1

Follow the steps in Section 7-7, wiring the UPS systems as shown

 

 

 

 

 

in the diagram.

 

 

 

 

2

Connect the included parallel UPS cable A to the parallel port B

 

 

B

6

 

 

 

 

of each UPS system.

 

 

 

 

 

 

 

B

A

7

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

7-9 AC Input/Output Wiring (Parallel UPS – Dual Input Sources)

 

 

8

Parallel UPS Warnings:

The total input cable length must be equal to the total output cable length in order to prevent unbalanced load sharing between two UPS systems under reserve mode (i.e. Res1 + OP1 = Res2 + OP2; deviation must be <10%).

Parallel configuration only supports 2 UPS systems (1+1 redundancy or capacity). Do not attempt to link more than two UPS systems via parallel configuration.

The UPS systems must have the same rating and capacity for parallel UPS installation. Attempting to

link dissimilar UPS systems will damage the UPS systems and create a serious risk of personal injury and property damage.

Each UPS must have its Parallel group set to 2 and a different “Parallel ID” that indicates the UPS systems are being run in parallel. (See Section 10-5-5for more details.)

1 Follow the steps in Section 7-7, wiring the UPS systems as shown in the diagram.

2 Connect the included parallel UPS cable A to the parallel port B of each UPS system.

 

 

9

 

 

10

1

 

11

 

 

 

B

12

B

A

13

 

 

 

2

 

 

 

 

14

21

Image 21
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesImportant Safety Instructions Location WarningsConnection Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Cabinet Installation PreparationUnpacking Shipping container. Warning The UPS system could tip if it PlacementRear, not from the sides Rear of the UPS systemSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring AC Input/Output Wiring Single UPS Failure to observe proper phase will damage the UPS systemCreate a risk of personal injury and property damage Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input SourceBattery Backup Mode Single UPS Online Normal Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSOnline Mode Parallel UPS Battery Backup Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSPreliminary Checklist Single UPS Control Panel and Breaker DiagramsStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display and Configuration Control Panel DiagramDisplay Hierarchy Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel Setup Parallel GroupParallel ID Control & Test Setup Battery Auto TestBuzzer Manual Battery Test Clear Battery Test ResultForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatAdministrator Password User PasswordLanguage Maintenance Firmware VersionStatistics Advance Use or to read the event log, then press toCommunications Communications InterfacesSnmpwebcard Slot Input Dry Contact Interface Auxiliary Dry Contact Input Circuit Diagram Remote Emergency Power Off EPO Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputDefault Messages Output Dry Contact Interface DetailOptional Messages 11-10 RS-232 Serial Port Circuit Diagram Output Dry Contact Circuit DiagramParallel Configuration Port Hardware Pin AssignmentUPS System Technical Specifications Optional Messages SpecificationsWarranty Storage and ServiceService Storage