6 – Internal Battery Connection (continued)

1

6-2 Internal Battery Connection Procedure (continued)

11 Use a voltmeter (user-supplied) to test the voltage of each internal battery pack. Observing proper polarity, connect the voltmeter’s black probe to the battery pack’s black connector; connect the voltmeter’s red probe to the battery pack’s red connector. Make sure the voltmeter’s probes touch the metal contacts inside the battery pack’s connectors. The battery pack’s acceptable DC voltage range is between 220V and 280V DC (nominal 240V DC). If several voltmeter tests yield results outside the acceptable DC voltage range, contact Tripp Lite for assistance in determining the possible causes of the incorrect voltage reading before proceeding.

 

2

 

3

11

4

 

12 Connect the black cable for each internal battery pack to the nearest black connector located inside the UPS system’s battery compartment. Connect the red cable for each internal battery pack to the nearest red connector located inside the UPS system’s battery compartment. Warning: Observe proper polarity by connecting negative to negative (black to black) and positive to positive (red to red). Failure to observe proper polarity will damage the UPS system and create a serious risk of personal injury and property damage.

5

6

12

13 Replace the battery access bezels.

14 Follow the proper procedure to restart the UPS and re-transfer the critical load to protected power.

Note: If you need to remove or replace internal battery packs, modify steps 6 and 7 by removing and/or replacing the existing internal battery packs, as required.

7

8

13

9

 

 

10

14

11

 

12

13

14

15

Image 15
Contents Not suitable for mobile applications Table of Contents Introduction Advanced FeaturesImportant Safety Instructions Location WarningsConnection Warnings Wiring Warnings Battery WarningsControl Panel Features Output Circuit Breaker Switch Q4 Controls AC output power Front and Rear Panel FeaturesFor more information about the Snmpwebcard accessory Cabinet Installation PreparationUnpacking Rear of the UPS system PlacementShipping container. Warning The UPS system could tip if it Rear, not from the sidesSU40KX shown Internal Battery Wiring DiagramsInternal Battery Connection Internal Battery Connection Procedure Type and rating Potential arcing of connectors. Blown fuses must be replacedInternal Battery Connection Wiring Preparation WiringExternal Battery Cabinet Wiring Diagrams UPS System Terminal Block DiagramElectrical and Cable Data External Battery CabinetsExternal Battery Cabinet Wiring AC Input/Output Wiring Single UPS Failure to observe proper phase will damage the UPS systemCreate a risk of personal injury and property damage Parallel UPS Warnings AC Input/Output Wiring Parallel UPS Single Input Source10 8-4 Manual Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS Auto Bypass Mode Single UPSOnline Mode Parallel UPS Battery Backup Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSStart-Up, Shutdown and Bypass Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display and Configuration Control Panel DiagramDisplay Hierarchy Status Display Default DisplayStatus Display Battery power Main Menu UPS System Measure Menu Administrator Qualified service personnel User UPS SetupBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Redundancy Press ESC to return to the UPS Setup menu Battery Setup10 3 Battery Strings Battery Next Replace Date Press ESC to return to the UPS Setup menuCharger Setup Parallel Setup Parallel GroupParallel ID Control & Test Setup Battery Auto TestBuzzer Manual Battery Test Clear Battery Test ResultForce Boost Charge Press ESC to return to the UPS Setup menu Local Setup LCD Contrast Date FormatAdministrator Password User PasswordLanguage Maintenance Firmware VersionStatistics Advance Use or to read the event log, then press toCommunications Communications InterfacesSnmpwebcard Slot Input Dry Contact Interface External Battery Status Input Remote Emergency Power Off EPO Circuit DiagramAuxiliary Dry Contact Input Circuit Diagram External Battery Cabinet Temperature InputsDefault Messages Output Dry Contact Interface DetailOptional Messages Hardware Pin Assignment Output Dry Contact Circuit Diagram11-10 RS-232 Serial Port Circuit Diagram Parallel Configuration PortUPS System Technical Specifications Optional Messages SpecificationsStorage Storage and ServiceWarranty Service