Tripp Lite SU40KX, SU80KX, SU20KX owner manual 10 3 Battery Strings

Page 44

110 – Display and Configuration (continued)

2

3

4

5

6

7

8

9

10-5-3 Battery Setup (continued)

1Enter the UPS system setup menu. Use the scroll buttons (,) to move the cursor to “BATTERY SETUP”, then press the enter button ().

At UPS startup, you must enter information about the battery, including amp hour rating, number of strings and charger current. Use the following formulas as a guide.

TYPE (AH) – Internal batteries are 9 AH per string. The AH rating for external batteries is equal to the number after the “V” in the model name. For example, BP480V26B = 26 AH. When internal and external batteries are used, total the values of each battery string. For example, SU40KX and BP480V26B = 58 AH (9+9+40).

BAT STRINGS – If only internal batteries are used, enter the number of strings. For example, SU40KX has two internal battery strings, so enter “2”. If both internal and external batteries are

used, do not count the internal battery. For example, SU40KX with 1 BP480V55, enter “1”.

CHARGER CURRENT – See Section 10-5-4for information about setting the charger current.

2From the “EXT BAT TYPE” screen, use the scroll buttons (, ) to select the desired settings and press the enter button () to confirm the settings. Note: See step 1 for additional guidance on AH settings.

BP480V26B = 26 AH BP480V40C = 40 AH BP480V55 = 55 AH BP480V78 = 78 AH BP480V103 = 103 AH BP480V140 = 140 AH

2

10 3 Battery Strings

Use “” or “” to select the desired number of battery strings, then press “ ” to confirm. Note: See step 1 for information about battery string settings.

11

12

13

3

14

44

Image 44
Contents Not suitable for mobile applications Table of Contents Advanced Features IntroductionConnection Warnings Important Safety InstructionsLocation Warnings Battery Warnings Wiring WarningsControl Panel Features Front and Rear Panel Features Output Circuit Breaker Switch Q4 Controls AC output powerFor more information about the Snmpwebcard accessory Unpacking Cabinet InstallationPreparation Placement Shipping container. Warning The UPS system could tip if itRear, not from the sides Rear of the UPS systemInternal Battery Wiring Diagrams SU40KX shownInternal Battery Connection Internal Battery Connection Procedure Potential arcing of connectors. Blown fuses must be replaced Type and ratingInternal Battery Connection Wiring Wiring PreparationUPS System Terminal Block Diagram External Battery Cabinet Wiring DiagramsExternal Battery Cabinets Electrical and Cable DataExternal Battery Cabinet Wiring Create a risk of personal injury and property damage AC Input/Output Wiring Single UPSFailure to observe proper phase will damage the UPS system AC Input/Output Wiring Parallel UPS Single Input Source Parallel UPS WarningsOnline Normal Mode Single UPS Battery Backup Mode Single UPSAuto Bypass Mode Single UPS 10 8-4 Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSControl Panel and Breaker Diagrams Preliminary Checklist Single UPSStandard Start-Up Procedure Single UPS Start-Up, Shutdown and BypassBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPS Shutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Display Hierarchy Display and ConfigurationControl Panel Diagram Default Display Status DisplayStatus Display Battery power Main Menu UPS System Measure Menu UPS Setup Administrator Qualified service personnel UserBypass Setup Press ESC to return to the UPS Setup menu Output Setup Output Voltage Press ESC to return to the UPS Setup menu Battery Setup Redundancy10 3 Battery Strings Press ESC to return to the UPS Setup menu Battery Next Replace DateCharger Setup Parallel ID Parallel SetupParallel Group Buzzer Control & Test SetupBattery Auto Test Force Boost Charge Manual Battery TestClear Battery Test Result Press ESC to return to the UPS Setup menu Local Setup Date Format LCD ContrastLanguage Administrator PasswordUser Password Statistics MaintenanceFirmware Version Use or to read the event log, then press to AdvanceSnmpwebcard Slot Input Dry Contact Interface CommunicationsCommunications Interfaces Remote Emergency Power Off EPO Circuit Diagram Auxiliary Dry Contact Input Circuit DiagramExternal Battery Cabinet Temperature Inputs External Battery Status InputOptional Messages Default MessagesOutput Dry Contact Interface Detail Output Dry Contact Circuit Diagram 11-10 RS-232 Serial Port Circuit DiagramParallel Configuration Port Hardware Pin AssignmentSpecifications UPS System Technical Specifications Optional MessagesStorage and Service WarrantyService Storage