Schneider Electric AP9635 manual Temperature and Humidity, Brief status, Threshold Description

Page 47

Temperature and Humidity Page

Brief status

Click Temp & Humidity on the left navigation menu to display the name, alarm status, temperature, and humidity (if supported) for each sensor.

Detailed status and configuration

Click the name of a sensor for detailed alarm status or to configure its values:

Identification and alarm status.

Parameter

Description

 

 

Name

A name for this sensor. Maximum: 20 characters.

 

 

Location

This physical location of the sensor. Maximum: 20 characters.

 

 

Alarm

One of the following is displayed:

Status

Normal if this sensor is not reporting an alarm condition.

 

• If this sensor is in an alarm state, the text of the alarm, indicating which threshold is violated,

 

and the severity of the alarm, indicated by color (red for critical, orange for warning).

 

 

Thresholds

See the next two sections for descriptions of the configurable thresholds and Hysteresis values.

 

 

Thresholds. For each sensor, you set the same types of thresholds for temperature and (if supported) humidity measured at the sensor.

Threshold

Description

 

 

Maximum

If the threshold for maximum temperature or for maximum humidity for the sensor is

 

exceeded, an alarm occurs.

 

 

High

If the threshold for high temperature or for high humidity for the sensor is exceeded, an alarm

 

occurs.

 

 

Low

If the temperature or humidity drops below its low threshold for the sensor, an alarm occurs.

 

 

Minimum

If the temperature or humidity drops below its minimum threshold for the sensor, an alarm

 

occurs.

 

 

Hysteresis. This value specifies how far past a threshold the temperature or humidity must return to clear a threshold violation.

For Maximum and High threshold violations, the clearing point is the threshold minus the hysteresis.

For Minimum and Low threshold violations, the clearing point is the threshold plus the hysteresis.

Increase the value for Temperature Hysteresis or Humidity Hysteresis to avoid multiple alarms if temperature or humidity that has caused a violation then wavers slightly up and down. If the hysteresis value is too low, such wavering can cause and clear a threshold violation repeatedly.

UPS Network Management Card 2 User’s Guide

38

Image 47
Contents User’s Guide 동봉된 CD 안에 한국어 매뉴얼이 있습니다 Contents Web Interface Monitor the UPS and Configure Shutdowns Logs Administration Notification Troubleshooting Appendix a List of Supported Commands Product Description FeaturesIntroduction Overview Internal Management FeaturesInitial setup Network management featuresTypes of user accounts Access priority for logging onHow to Recover from a Lost Password Description Front PanelLink-RX/TX 10/100 LED Status LEDCondition Description Network interface watchdog mechanism Watchdog FeaturesResetting the network timer Remote access to the command line interface Command Line InterfaceHow To Log On Information and status fields Main ScreenSample main screen Two fields report when you logged in, by date and time Command syntax Using the Command Line InterfaceEntering commands Syntax examples Command Response CodesCode Error message Option Arguments Description Command DescriptionsAlarmcount AboutOption Argument Description BootDate ConsoleDns DeleteArgument Description DirFormat EventlogKey Description ExitModbus FtpOption Argument Definition HelpPing NetstatNtp Quit PortSpeedPrompt Radius RebootSystem ResetToDefSnmp, snmp3 Tcpip6 TcpipTls Ups UioUser XferStatus WebXferINI Supported Web browsers Web InterfaceIntroduction URL address formats Error Message Browser Cause of the ErrorRecent Device Events HomeQuick status icons Icon DescriptionQuick Links How to Use the Tabs, Menus, and LinksTabs MenusOperating State Icon Description Monitor the UPS and Configure ShutdownsOverview Operating stateModel-specific status displayed StatusRecent UPS Events PowerChute Network Shutdown clients PowerChute Option Parameter Description PowerChute Network Shutdown configuration parametersAbout Option Heading Displayed Information Environmental MonitoringThreshold Description Temperature and HumidityDetailed status and configuration Brief statusUPS Network Management Card 2 User’s Guide Input Contacts About Output RelayConfiguring the UPS or output to respond to an input alarm Configuring the Control PolicyConfiguring an output to respond to an event Launch Log in New Window button LogsUse the Event and Data Logs Event logData log To display the data log Logs Data log To set the data collection interval Logs Data interval How to use FTP or SCP to retrieve log files Scp username@hostnameoripaddressevent.csv ./event.csv Syslog servers Local Users Administration SecuritySetting user access AuthenticationRadius Radius Setting DefinitionSupported Radius servers Configuring the Radius ServerSummary of the configuration procedure Configuring a Radius server on Unix with shadow passwordsInactivity Timeout Setting Description Administration Network FeaturesTCP/IP and Communication Settings TCP/IP settingsAPC Cookie. Tag 1, Len 4, Data 1APC Dhcp response optionsPing Response DNS Port SpeedQuery Type Selected Query Question to Use Option Description WebConsole SNMPv1 SnmpSNMPv3 Modbus FTP Server Types of notification Administration NotificationConfiguring event actions Event ActionsNetwork Management Card User’s Guide Mail notification Active, Automatic, Direct NotificationIdentify up to four e-mail recipients Snmp Trap Test Snmp trapsSyslog Remote Monitoring ServiceSetting Definition Syslog Settings Path Logs Syslog settings Method Administration General OptionsIdentification Set the Date and TimeDaylight saving Use an .ini FileColor-code event log text Event Log, Temperature Units, and Log-InChange the default temperature scale Specify a default loginAction Definition Reset the Management CardConfigure Links About the Management CardInstallation Device IP Configuration WizardCapabilities, Requirements, and Installation How to use the Wizard to configure TCP/IP settingsSelect Remotely over the network, and click Next Configure the basic TCP/IP settings remotelyUse the Wizard Select Locally through the serial port, and click Next Configure or reconfigure the TCP/IP settings locallyDetailed procedures How to Export Configuration SettingsSummary of the procedure Contents of the .ini fileFtp put filename.ini Errors generated by overridden values Upload Event and Error MessagesEvent and its error messages Messages in config.iniRelated Topics Firmware files Network Management Card How to Upgrade FirmwareFile Transfers Benefits of upgrading firmwareFirmware File Transfer Methods Use FTP or SCP to upgrade one Management CardHow to upgrade multiple Management Cards Use Xmodem to upgrade one Management Card Verify the success or failure of the transfer Verifying Upgrades and UpdatesVerify the version numbers of installed firmware Use a USB drive to transfer the filesAdding and Changing Language Packs Problem Solution TroubleshootingManagement Card Access Problems GET Snmp IssuesAppendix a List of Supported Commands Network Management Card User’s Guide Network Management Card User’s Guide Non-transferable warranty Exclusions Two-Year Factory WarrantyTerms of warranty Warranty claims 990-3197B-001 2011 APC Worldwide Customer Support