Liebert XDP user manual Field Connections-All Units, Field Connections-Optional for All Units

Page 16

Product Description

Field Connections—All Units

Connect the control display panel cable to terminal block TB3 terminals 1 through 4 on the Lie- bert XDP control board as shown (refer to Figure 15). The display panel may be mounted on the Liebert XDP’s front right door if the Liebert XDP is located in the area that it conditions. The dis- play panel must always be installed in the conditioned space.

Connect the provided remote temperature / humidity sensor extension cable to the factory-installed cable connected to P16 on the control board. Install the sensor in the higher- temperature portion of the cold aisle where the XD modules are located. Alternatively, it can be placed on the return air side of the primary air mover (e.g., Liebert Deluxe System/3) in the room if it represents the conditions where all the XD cooling modules are located. Do not install the sensor where ambient air may cause false readings, for example, near unsealed doors, windows and similar areas.

Field Connections—Optional for All Units

Connect field wiring from the optional Liebert XD cooling module condensation detection circuit to terminal strip locations H2O (24) and XDOC (51).

Connect optional field wiring from remote devices to remote alarm device, common alarm output, site monitor and remote shutdown, if applicable. See terminal strip descriptions in Figure 15.

Figure 15 Liebert XDP extra low voltage field connections points

 

Temperature/Humidity Sensor

 

Cable Provided with

 

Control Display Panel

Temperature/Humidity Sensor Board

 

 

Four thermostatic wires

 

 

to be connected toTB3

 

 

 

TS-3

Factory-Wired

 

Temperature

 

TS-4

 

Sensor(s)

 

TS-5

 

TS-6

 

 

 

H2O (24)

 

 

RAD1 (50)

 

 

XDOC (51)

 

 

K3COM

 

 

K3NO

 

 

K3NCL

 

 

37

 

 

38

 

 

77

 

 

78

Control wiring must be Class 2 and installed

 

 

in accordance with the National Electrical Code (NEC)

 

Requires shielded cable

 

 

 

10

 

Image 16
Contents Liebert XDP General Safety Guidelines Example XDP160AFluorinated Greenhouse Gas Requirements-European Union Pumping Place holder Revision Unit Redundancy Level LiebertTable of Contents Alarm Descriptions and Solutions SpecificationsFigures Page General Product Information Equipment InspectionProduct Description Product/System DescriptionHandling With Skid Equipment HandlingRemoval from Skid Removing pallet boards for piano jack insertion Liebert XDP strapped to piano jackRemoving Piano Jacks Slide this runner away From the Liebert XDPMechanical Considerations Liebert XDP dimensionsPositioning the Liebert XDP Unit piping outlet connection sizes, inches, OD Cu Model Pipe Connection Point 50/60 HzConnecting High-Voltage Cables Electrical Information High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Extra Low Voltage ELV Connections High voltage connections-50HzField Connections-All Units Field Connections-Optional for All UnitsEuropean Union Fluorinated Greenhouse Gas Requirements Connection SizesPiping Recommended Pipe SizePiping Installation Method Liebert XDP Interconnection with Liebert XD Cooling ModulesBypass Flow Controller Bypass flow controllers for a Liebert XDP-based systemBypass flow controller details, dimensions Bypass flow controller arrangementPiping Installation Method Piping Details-Shut-Off/Isolation ValvesPiping Mains Evacuation and Leak CheckChecklist for Proper Installation Liebert XDP pump light indicator-208V and 400V units Checklist for Liebert XDP StartupIndicator Lights Description Green Red Filling the Pumped Circuit-R-134a System R-134a liquid levelReturn Line Diameter 5/8 System refrigerant charge for the supply and return mainsReturn Line Diameter Calculating Refrigerant Charge-Example Calculating refrigerant charge-exampleWorksheet to calculate refrigerant charge Total 293Feature Overview Microprocessor ControlDisplay User interface keypad functionsFeature Overview Viewing or Changing SettingsControls Main MenuActive Alarms Alarm HistorySetpoints MIN Temp SPSetup Operation Restart Time DelayDegrees Pump Start TDLiebert XDP DIP switches and factory settings Pump Wait TDPump OFF TD Lead PumpChange Password-SETPT Password Password Security-SETPT Password and Service PasswordValve Time Change Password-SERVICE Password Alarm EnableAlarm Time Delay COM Alarm EnableDiagnostics Custom AlarmsCustom Text Alarm Descriptions Alarm Descriptions and SolutionsAlter Alarm Settings Red and Green Lamp IndicatorsEnable or Disable Alarms System Shutdown Causes Troubleshooting Troubleshooting the XDPMaintenance Fluorinated Greenhouse Gas RequirementsSpecifications Liebert XDP160 specificationsNe t ItiTi n That