Liebert Liebert XDP Interconnection with Liebert XD Cooling Modules, Bypass Flow Controller

Page 18

Piping

2.3Liebert XDP Interconnection with Liebert XD Cooling Modules

All piping must be ASTM (American Society for Testing and Materials) Type L copper pipe.

The Liebert XDP may be connected to Liebert XD cooling modules with either Liebert’s XD prefabri- cated piping assembly or with rigid, off-the-shelf piping. In either setup, piping for the Liebert XD system is arranged in a manner similar to piping for a chilled water system. Liebert XD cooling mod- ules are connected in parallel between main return and supply pipes going to and from the Liebert XDP/Liebert XDC. For piping details, refer to Liebert’s XD System Design Manual, SL-16655. The guidelines provided for pipe size must be strictly followed. Failure to size the main lines and connection lines adequately may result in reduced cooling capacity. The critical aspects of pipe sizing are related to refrigerant volume and pressure drop. Both must be minimized.

Figure 16 Piping arrangement for Liebert XDP/Liebert XDC used with Liebert XD cooling modules

Liebert XDP/ Liebert XDC

 

 

 

 

 

All supply and

 

 

 

 

 

return mains

Liebert XD

Liebert XD

Liebert XD

Liebert XD

Liebert XD

must be level with

Cooling

Cooling

Cooling

Cooling

Cooling

or above the top

Modules

Modules

Modules

Modules

Modules

of all Liebert

 

 

 

 

 

 

 

 

 

 

XD modules

SLOPE—The main supply and return lines to and from the Liebert XDP/Liebert XDC must be sloped downward toward the Liebert XDP/Liebert XDC at a rate of 1-2" per 20 feet (25.4-51mm per 6m) of pipe run. Horizontal connector lines should also be sloped downward from the cooling modules toward the main supply and return lines.

2.4Piping Installation Method

The assembly and connection means used for piping in the Liebert XD system are similar to that of conventional refrigeration systems. All piping should be installed with high-temperature brazed joints. Brazing material may be used, but soft soldering is not recommended. If brazing material is used, the lines being brazed MUST be filled with flowing dry nitrogen during brazing to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices should be employed for piping supports, leak testing, dehydration and charging.

Insulate all piping lines to prevent condensation in applications where the dew point approaches the R-134a refrigerant temperature.

2.4.1Bypass Flow Controller

Some installations require one or more bypass flow controller(s) to ensure that the Liebert XDP’s pumps operate within the optimum range. These devices are added to the field piping and simulate the flow of additional cooling modules.

Each bypass flow controller should be installed with one shutoff valve to allow the controller to be dis- abled when cooling modules are added to a Liebert XD system.

If bypass flow controllers are required, they should be connected between the main supply and the main return lines of the field piping. The connection points to the main supply and return lines should be in a convenient and accessible location between the Liebert XDP and the first Liebert XD module in the circuit. See Figures 17 and 18 for piping details of the bypass flow controller.

Refer to Table 4 to determine the number of bypass flow controllers needed, based on the total nomi- nal cooling capacity of the cooling modules in each Liebert XD system.

Table 4 Bypass flow controllers for a Liebert XDP-based system

 

Required Number

Cooling Modules -

of Bypass Flow Controllers

 

Cumulative Model Size

Liebert XDP

32 to 63

3

 

 

64 to 95

2

 

 

96 to 127

1

 

 

128 to 160

0

 

 

12

Image 18
Contents Liebert XDP Fluorinated Greenhouse Gas Requirements-European Union General Safety GuidelinesExample XDP160A Pumping Place holder Revision Unit Redundancy Level LiebertTable of Contents Alarm Descriptions and Solutions SpecificationsFigures Page Product Description General Product InformationEquipment Inspection Product/System DescriptionEquipment Handling Handling With SkidRemoval from Skid Removing pallet boards for piano jack insertion Liebert XDP strapped to piano jackRemoving Piano Jacks Slide this runner away From the Liebert XDPLiebert XDP dimensions Mechanical ConsiderationsPositioning the Liebert XDP Unit piping outlet connection sizes, inches, OD Cu Model Pipe Connection Point 50/60 HzConnecting High-Voltage Cables Electrical Information High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Extra Low Voltage ELV Connections High voltage connections-50HzField Connections-All Units Field Connections-Optional for All UnitsPiping European Union Fluorinated Greenhouse Gas RequirementsConnection Sizes Recommended Pipe SizeBypass Flow Controller Piping Installation MethodLiebert XDP Interconnection with Liebert XD Cooling Modules Bypass flow controllers for a Liebert XDP-based systemBypass flow controller details, dimensions Bypass flow controller arrangementPiping Mains Piping Installation MethodPiping Details-Shut-Off/Isolation Valves Evacuation and Leak CheckChecklist for Proper Installation Checklist for Liebert XDP Startup Liebert XDP pump light indicator-208V and 400V unitsIndicator Lights Description Green Red Filling the Pumped Circuit-R-134a System R-134a liquid levelSystem refrigerant charge for the supply and return mains Return Line Diameter 5/8Return Line Diameter Worksheet to calculate refrigerant charge Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Total 293Display Feature OverviewMicroprocessor Control User interface keypad functionsControls Feature OverviewViewing or Changing Settings Main MenuSetpoints Active AlarmsAlarm History MIN Temp SPDegrees Setup OperationRestart Time Delay Pump Start TDPump OFF TD Liebert XDP DIP switches and factory settingsPump Wait TD Lead PumpPassword Security-SETPT Password and Service Password Change Password-SETPT PasswordValve Time Alarm Time Delay Change Password-SERVICE PasswordAlarm Enable COM Alarm EnableCustom Alarms DiagnosticsCustom Text Alarm Descriptions Alarm Descriptions and SolutionsRed and Green Lamp Indicators Alter Alarm SettingsEnable or Disable Alarms System Shutdown Causes Troubleshooting Troubleshooting the XDPMaintenance Fluorinated Greenhouse Gas RequirementsSpecifications Liebert XDP160 specificationsTi n Ne tIti That