Liebert XDP Calculating Refrigerant Charge-Example, Calculating refrigerant charge-example

Page 25

Checklist for Liebert XDP Startup

3.1.1Calculating Refrigerant Charge—Example

Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF, Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20 Liebert XDV8 cooling modules.

Table 10 Calculating refrigerant charge—example

 

Number of Units

 

 

 

or Piping Length,

Pounds Per

 

Components

feet

Component

Total, lb.

Liebert XDP

1

157

157

 

 

 

 

Liebert XDV8 Cooling Modules

20

2.32

46.4

 

 

 

 

Supply Main, 1-1/8"

100

0.45

45

 

 

 

 

Return Main, 2-1/8"

100

0.28

28

 

 

 

 

Liebert XDV 1/2" supply Liebert XD Flex Pipes

20

0.8

16

 

 

 

 

Liebert XDV 5/8" return Liebert XD Flex Pipes

20

0.03

0.6

 

 

 

 

 

 

Total

293

Table 11 Worksheet to calculate refrigerant charge

Components

Number of Units or Piping Length

Pounds Per Component

Total

Total

19

Image 25
Contents Liebert XDP Example XDP160A General Safety GuidelinesFluorinated Greenhouse Gas Requirements-European Union Pumping Place holder Revision Unit Redundancy Level LiebertTable of Contents Specifications Alarm Descriptions and SolutionsFigures Page Equipment Inspection General Product InformationProduct Description Product/System DescriptionHandling With Skid Equipment HandlingRemoval from Skid Liebert XDP strapped to piano jack Removing pallet boards for piano jack insertionSlide this runner away From the Liebert XDP Removing Piano JacksMechanical Considerations Liebert XDP dimensionsPositioning the Liebert XDP Model Pipe Connection Point 50/60 Hz Unit piping outlet connection sizes, inches, OD CuElectrical Information High Voltage Connections Connecting High-Voltage CablesElectrical enclosure knockout locations for field wiring High voltage connections-50Hz Extra Low Voltage ELV ConnectionsField Connections-Optional for All Units Field Connections-All UnitsConnection Sizes European Union Fluorinated Greenhouse Gas RequirementsPiping Recommended Pipe SizeLiebert XDP Interconnection with Liebert XD Cooling Modules Piping Installation MethodBypass Flow Controller Bypass flow controllers for a Liebert XDP-based systemBypass flow controller arrangement Bypass flow controller details, dimensionsPiping Details-Shut-Off/Isolation Valves Piping Installation MethodPiping Mains Evacuation and Leak CheckChecklist for Proper Installation Liebert XDP pump light indicator-208V and 400V units Checklist for Liebert XDP StartupIndicator Lights Description Green Red System R-134a liquid level Filling the Pumped Circuit-R-134aReturn Line Diameter 5/8 System refrigerant charge for the supply and return mainsReturn Line Diameter Calculating refrigerant charge-example Calculating Refrigerant Charge-ExampleWorksheet to calculate refrigerant charge Total 293Microprocessor Control Feature OverviewDisplay User interface keypad functionsViewing or Changing Settings Feature OverviewControls Main MenuAlarm History Active AlarmsSetpoints MIN Temp SPRestart Time Delay Setup OperationDegrees Pump Start TDPump Wait TD Liebert XDP DIP switches and factory settingsPump OFF TD Lead PumpChange Password-SETPT Password Password Security-SETPT Password and Service PasswordValve Time Alarm Enable Change Password-SERVICE PasswordAlarm Time Delay COM Alarm EnableDiagnostics Custom AlarmsCustom Text Alarm Descriptions and Solutions Alarm DescriptionsAlter Alarm Settings Red and Green Lamp IndicatorsEnable or Disable Alarms System Shutdown Causes Troubleshooting the XDP TroubleshootingFluorinated Greenhouse Gas Requirements MaintenanceLiebert XDP160 specifications SpecificationsIti Ne tTi n That