Liebert Comprehensive Troubleshooting for the XDP and Thermostat Password Help

Page 37

Troubleshooting

6.0TROUBLESHOOTING

Table 16 Troubleshooting the XDP

Symptom

Possible Cause

Check or Remedy

 

No main power

Check L1, L2 and L3 for rated voltage.

 

Loose electrical connections

Tighten connections.

Pump will not energize

Overloads tripped

Allow pump to cool. Check amp draw.

 

 

 

 

Tripped circuit breaker

Check circuit breaker to pump(s).

 

 

 

 

Incorrect phase wiring

See Table 5.

 

No chilled water

Check and verify that there is supply chilled water to the

 

Liebert XDP.

 

 

 

Isolation valve(s) on pump suction

Open all isolation valves completely during normal

 

and/or discharge is closed.

operation.

Pump will not run

Supply chilled water is too high

Check and verify that the chilled water temperature

 

setpoint is at 50°F (10°C) or lower and that there is flow

 

 

on the chilled water side.

 

Liebert XD cooling modules are Off

Check Liebert XD cooling module to make sure that they

 

are On prior to starting the Liebert XDP.

 

 

 

 

Check alarm(s) history on Liebert XDP. The Liebert XDP

 

 

was operating below the dew point for a significant

 

Low Refrigerant Temperature (high

amount of time. Check humidity in conditioned space,

 

lower humidity if necessary to allow Liebert XDP to

 

dew point)

 

operate at a lower temperature. (Disconnect must be

 

 

 

 

switched to Off then back On to allow Liebert XDP to

 

 

reset itself).

 

 

Place the sensor on the RETURN AIR side of the primary

 

Incorrect location of

air mover (e.g., Liebert Deluxe System 3). Do not install

 

temperature-humidity sensors

the sensor near unsealed doors, windows and similar

 

 

areas.

 

 

Check both differential pressure settings. If not within

 

Pressure switch not making contact

6 psi, ±1 psi (41kPa, ±7kPa; 0.41 bars, ±0.07bars) then

 

 

manually change accordingly.

 

Not enough charge

See 3.0 - Checklist for Liebert XDP Startup.

 

Cavitation due to vapor in pump

Check for adequate charge in system, refer to the User's

Pump noisy

Manual. 3.0 - Checklist for Liebert XDP Startup

 

 

Worn motor bearings

Replace pump

 

 

 

 

Low Refrigerant Temperature (High

Check humidity of room along with location of remote

Liebert XDP (Pump)

sensors. Make sure that the sensors are not located in a

dew point)

suddenly stops

cold area where there is a lack of sufficient air flow.

 

 

Clogged filter/dryer and/or impeller

Clean out debris.

 

 

 

Pipe rattle

Loose pipe connections

Check pipe connections

 

 

 

Chilled water valve not

Motor operates but valve won't open

Check linkage for adjustment and be sure that it is tight on

working

the valve.

 

 

No 24 VAC power to motor

Check for 24 VAC between P2-1 and P2-4.

 

 

 

 

No signal from control

Check 24 VAC at P22-1 (close) or P22-3 (open).

 

 

 

Actuator motors

 

Unplug P22 completely off of the board. Jumper P22-5 to

 

Motor not operating

P2-4 for grounding, then jumper P22-1 to P2-1 to drive

 

close. Remove jumper to close, and then jumper P22-3 to

 

 

 

 

P2-1 to drive open. If motor fails to work, replace it.

 

 

 

 

Check control panel for welded

 

Motor burnout

contactor contacts or welded

Replace defective components.

 

overload contacts

 

Main 24 VAC fuse trips

Shorts or loose connections

Check the wiring connections of the 24 VAC circuit.

 

 

Faulty circuit board

Replace the circuit board.

 

 

 

 

Unstable pump

R-134a pump loop is overcharged

While pump is running R-134a receiver level must be

operation

within recommended levels (see Figure 21).

 

31

Image 37
Contents Liebert XDP Example XDP160A General Safety GuidelinesFluorinated Greenhouse Gas Requirements-European Union Pumping Place holder Revision Unit Redundancy Level LiebertTable of Contents Specifications Alarm Descriptions and SolutionsFigures Page Equipment Inspection General Product InformationProduct Description Product/System DescriptionHandling With Skid Equipment HandlingRemoval from Skid Liebert XDP strapped to piano jack Removing pallet boards for piano jack insertionSlide this runner away From the Liebert XDP Removing Piano JacksMechanical Considerations Liebert XDP dimensionsPositioning the Liebert XDP Model Pipe Connection Point 50/60 Hz Unit piping outlet connection sizes, inches, OD CuElectrical Information High Voltage Connections Connecting High-Voltage CablesElectrical enclosure knockout locations for field wiring High voltage connections-50Hz Extra Low Voltage ELV ConnectionsField Connections-Optional for All Units Field Connections-All UnitsConnection Sizes European Union Fluorinated Greenhouse Gas RequirementsPiping Recommended Pipe SizeLiebert XDP Interconnection with Liebert XD Cooling Modules Piping Installation MethodBypass Flow Controller Bypass flow controllers for a Liebert XDP-based systemBypass flow controller arrangement Bypass flow controller details, dimensionsPiping Details-Shut-Off/Isolation Valves Piping Installation MethodPiping Mains Evacuation and Leak CheckChecklist for Proper Installation Liebert XDP pump light indicator-208V and 400V units Checklist for Liebert XDP StartupIndicator Lights Description Green Red System R-134a liquid level Filling the Pumped Circuit-R-134aReturn Line Diameter 5/8 System refrigerant charge for the supply and return mainsReturn Line Diameter Calculating refrigerant charge-example Calculating Refrigerant Charge-ExampleWorksheet to calculate refrigerant charge Total 293Microprocessor Control Feature OverviewDisplay User interface keypad functionsViewing or Changing Settings Feature OverviewControls Main MenuAlarm History Active AlarmsSetpoints MIN Temp SPRestart Time Delay Setup OperationDegrees Pump Start TDPump Wait TD Liebert XDP DIP switches and factory settingsPump OFF TD Lead PumpChange Password-SETPT Password Password Security-SETPT Password and Service PasswordValve Time Alarm Enable Change Password-SERVICE PasswordAlarm Time Delay COM Alarm EnableDiagnostics Custom AlarmsCustom Text Alarm Descriptions and Solutions Alarm DescriptionsAlter Alarm Settings Red and Green Lamp IndicatorsEnable or Disable Alarms System Shutdown Causes Troubleshooting the XDP TroubleshootingFluorinated Greenhouse Gas Requirements MaintenanceLiebert XDP160 specifications SpecificationsIti Ne tTi n That