Microprocessor Control
4.3.2SETPOINTS
Selecting SETPOINTS from the Main Menu will reveal the following menu items:
Table 13 Setpoint functions, default values and allowable ranges
Menu Item | Function | Default, °F (°C) | Range, °F (°C) |
MIN TEMP SP | Minimum room temperature setpoint | 72 (22) | |
HI CW TEMP | High chilled water temperature setpoint | 55 (13) | 35 to 95 |
HI AIR TEMP | High room air temperature setpoint | 80 (27) | 35 to 95 |
LO AIR TEMP | Low room air temperature setpoint | 65 (18) | 35 to 95 |
*For optimal cooling performance, the minimum temperature setpoint should be at least
MIN TEMP SP
Minimum Room Temperature
NOTE
This is not a true room temperature setpoint. The Liebert XDP has no heaters; it will try to cool as much as possible. If it is able to cool the room to this setpoint, it will back off its cooling capability to try to keep the room temperature at or above this setpoint.
HIGH CW TEMP
High Chilled Water Temperature
HI AIR TEMP
High Room Air Temperature
LOW AIR TEMP
Low Room Air Temperature
4.3.3STATUS
The user can check the status of the control valve, pump operation, and refrigerant and chilled water temperature.
CONTROL
PUMP
REFRIG
4.3.4ACTIVE ALARMS
This submenu allows the user to review any present alarms. If no alarms are present, the screen will read “No Alarms Present.” If any alarms are occurring, the screen will display “Alarm XX of YY,” followed by the alarm text (“XX” is the reference number of the alarm shown, “YY” is the total number of alarms).
If more than one alarm is present, use the Up or Down arrow keys to scroll through the alarms.
4.3.5ALARM HISTORY
This submenu allows the user to review the 60