Liebert XDP Change Password-SERVICE Password, Calibrate Sensor, Alarm Enable, Alarm Time Delay

Page 32

Microprocessor Control

Change Password—SERVICE PASSWORD

The factory default SERVICE PASSWORD is “123”—this password protects setup operations and more-critical alarm settings. To change the SERVICE PASSWORD:

1.Press the MENU key to display the Main Menu.

2.Use the Up or Down arrow key to scroll to the SERVICE PASSWORD function.

3.Press ENTER to access the SERVICE PASSWORD function. The LCD will display three zeros (000).

4.Enter the present, three-digit password.

a.Use the Up or Down arrow key to enter the first number.

b.Press the ENTER button to select the second number in the password.

c.Use the Up or Down arrow key to enter the second number.

d.Enter the third number by repeating Steps b and c.

e.Press the ENTER button to accept the password. The LCD will display the message

PASSWORD OK.

5.Press the ENTER button; the LCD displays the message ENTER NEW PSW and the current password. The first numeral will be selected.

6.Use the Up or Down arrow key to enter the first number of the new password. Press the ENTER button to select the second numeral in the password.

7.Use the Up or Down arrow key to enter the second number of the new password. Press the ENTER button to select the third numeral in the password.

8.Use the Up or Down arrow key to enter the third number of the new password. Press the ENTER button to save the new password.

4.3.10CALIBRATE SENSOR

The local and the remote temperature and humidity sensors can be calibrated by selecting this menu item. The temperature sensor can be calibrated ± 5°F and the humidity sensor can be calibrated ±10% RH. To prevent coil condensation that could damage the Liebert XDP, the sensors must be cali- brated to a known source.

4.3.11ALARM ENABLE

Some alarms can be disabled or enabled as part of the user’s customized setup. An alarm that has been disabled will not report to the wall box beeper nor to the common alarm relay. Alarms are enabled by default.

Use the Up or Down arrow key to select a particular alarm; “YES” enables the alarm, “NO” disables the alarm. Press ENTER to save the change.

4.3.12ALARM TIME DELAY

Some alarms can be programmed with a time delay as a means of preventing nuisance alarms. This function specifies the amount of time an alarm must be present before the Liebert XDP recognizes and annunciates the alarm. If the alarm condition goes away before the time delay has expired, the alarm will not be recognized, and the time delay timer will be reset.

4.3.13COM ALARM ENABLE

Each individual alarm can be selected to energize or not to energize the common alarm relay. If the energize common alarm function is set to YES, the relay is energized immediately as the alarm is annunciated and de-energized when the alarm condition goes away (only after the alarm has been recognized). If the alarm is completely DISABLED, the alarm has no effect on the common alarm relay.

Use the Up or Down arrow key to scroll to a particular alarm, press the ENTER button to select it, then press the ENTER button to change the state (Yes or No).

26

Image 32
Contents Liebert XDP General Safety Guidelines Example XDP160AFluorinated Greenhouse Gas Requirements-European Union Pumping Place holder Revision Unit Redundancy Level LiebertTable of Contents Alarm Descriptions and Solutions SpecificationsFigures Page General Product Information Equipment InspectionProduct Description Product/System DescriptionRemoval from Skid Equipment HandlingHandling With Skid Removing pallet boards for piano jack insertion Liebert XDP strapped to piano jackRemoving Piano Jacks Slide this runner away From the Liebert XDPPositioning the Liebert XDP Liebert XDP dimensionsMechanical Considerations Unit piping outlet connection sizes, inches, OD Cu Model Pipe Connection Point 50/60 HzConnecting High-Voltage Cables Electrical Information High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Extra Low Voltage ELV Connections High voltage connections-50HzField Connections-All Units Field Connections-Optional for All UnitsEuropean Union Fluorinated Greenhouse Gas Requirements Connection SizesPiping Recommended Pipe SizePiping Installation Method Liebert XDP Interconnection with Liebert XD Cooling ModulesBypass Flow Controller Bypass flow controllers for a Liebert XDP-based systemBypass flow controller details, dimensions Bypass flow controller arrangementPiping Installation Method Piping Details-Shut-Off/Isolation ValvesPiping Mains Evacuation and Leak CheckChecklist for Proper Installation Indicator Lights Description Green Red Checklist for Liebert XDP StartupLiebert XDP pump light indicator-208V and 400V units Filling the Pumped Circuit-R-134a System R-134a liquid levelReturn Line Diameter System refrigerant charge for the supply and return mainsReturn Line Diameter 5/8 Calculating Refrigerant Charge-Example Calculating refrigerant charge-exampleWorksheet to calculate refrigerant charge Total 293Feature Overview Microprocessor ControlDisplay User interface keypad functionsFeature Overview Viewing or Changing SettingsControls Main MenuActive Alarms Alarm HistorySetpoints MIN Temp SPSetup Operation Restart Time DelayDegrees Pump Start TDLiebert XDP DIP switches and factory settings Pump Wait TDPump OFF TD Lead PumpValve Time Password Security-SETPT Password and Service PasswordChange Password-SETPT Password Change Password-SERVICE Password Alarm EnableAlarm Time Delay COM Alarm EnableCustom Text Custom AlarmsDiagnostics Alarm Descriptions Alarm Descriptions and SolutionsEnable or Disable Alarms Red and Green Lamp IndicatorsAlter Alarm Settings System Shutdown Causes Troubleshooting Troubleshooting the XDPMaintenance Fluorinated Greenhouse Gas RequirementsSpecifications Liebert XDP160 specificationsNe t ItiTi n That