Liebert XDP user manual General Product Information, Equipment Inspection, Product Description

Page 7

Product Description

1.0PRODUCT DESCRIPTION

1.1General Product Information

1.1.1Product/System Description

Liebert’s XDP refrigerant distribution unit is an interface between the building chilled water system and the cooling modules in the Liebert XD system. It is designed to circulate and control refrigerant to the cooling modules that are in the room with heat-producing equipment. The Liebert XDP consists of a cabinet that includes a heat exchanger, circulating pump(s), control valve, receiver, controls, valves and piping.

The Liebert XDP monitors room conditions and prevents coil condensation by maintaining the refrig- erant being pumped to the cooling modules at a temperature above the room’s dew point.

All functions, such as switching pumps (if applicable), controlling refrigerant temperature, etc., are automatic.

The Liebert XDP’s minimum recommended operating load is 20% of system nominal capacity. For example, a Liebert XDP160 60Hz system’s minimum load would be 32 kW. Loading below this value can unfavorably affect system operation. Consult factory for any loading below this recommendation.

The Liebert XDP is rated for 160kW (546,000 BTU/H) of cooling.

Figure 1 Liebert XDP components

Liebert XDP Unit

Control Valve

Chilled Water

Liebert XD Cooling Modules

Heat Exchanger

Receiver Pumps

1.2Equipment Inspection

When the unit is delivered, inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative.

1

Image 7
Contents Liebert XDP Pumping Place holder Revision Unit Redundancy Level Liebert General Safety GuidelinesExample XDP160A Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Specifications Alarm Descriptions and SolutionsFigures Page Product/System Description General Product InformationEquipment Inspection Product DescriptionHandling With Skid Equipment HandlingRemoval from Skid Liebert XDP strapped to piano jack Removing pallet boards for piano jack insertionSlide this runner away From the Liebert XDP Removing Piano JacksMechanical Considerations Liebert XDP dimensionsPositioning the Liebert XDP Model Pipe Connection Point 50/60 Hz Unit piping outlet connection sizes, inches, OD CuElectrical Information High Voltage Connections Connecting High-Voltage CablesElectrical enclosure knockout locations for field wiring High voltage connections-50Hz Extra Low Voltage ELV ConnectionsField Connections-Optional for All Units Field Connections-All UnitsRecommended Pipe Size European Union Fluorinated Greenhouse Gas RequirementsConnection Sizes PipingBypass flow controllers for a Liebert XDP-based system Piping Installation MethodLiebert XDP Interconnection with Liebert XD Cooling Modules Bypass Flow ControllerBypass flow controller arrangement Bypass flow controller details, dimensionsEvacuation and Leak Check Piping Installation MethodPiping Details-Shut-Off/Isolation Valves Piping MainsChecklist for Proper Installation Liebert XDP pump light indicator-208V and 400V units Checklist for Liebert XDP StartupIndicator Lights Description Green Red System R-134a liquid level Filling the Pumped Circuit-R-134aReturn Line Diameter 5/8 System refrigerant charge for the supply and return mainsReturn Line Diameter Total 293 Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Worksheet to calculate refrigerant chargeUser interface keypad functions Feature OverviewMicroprocessor Control DisplayMain Menu Feature OverviewViewing or Changing Settings ControlsMIN Temp SP Active AlarmsAlarm History SetpointsPump Start TD Setup OperationRestart Time Delay DegreesLead Pump Liebert XDP DIP switches and factory settingsPump Wait TD Pump OFF TDChange Password-SETPT Password Password Security-SETPT Password and Service PasswordValve Time COM Alarm Enable Change Password-SERVICE PasswordAlarm Enable Alarm Time DelayDiagnostics Custom AlarmsCustom Text Alarm Descriptions and Solutions Alarm DescriptionsAlter Alarm Settings Red and Green Lamp IndicatorsEnable or Disable Alarms System Shutdown Causes Troubleshooting the XDP TroubleshootingFluorinated Greenhouse Gas Requirements MaintenanceLiebert XDP160 specifications SpecificationsThat Ne tIti Ti n