Liebert XDP user manual Custom Alarms, Custom Text, Diagnostics

Page 33

Microprocessor Control

4.3.14CUSTOM ALARMS

This is the menu where the user selects the alarm message that will be displayed when there is an input to the customer alarm input on the control board. This menu has four choices: one user-defined custom message (see CUSTOM TEXT below for details) and three preprogrammed messages:

SMOKE DETECTED

CUSTOM 1 (default custom message. If the user enters a custom text message, that custom text will replace “CUSTOM 1.”)

WATER FLOW LOSS

STANDBY UNIT ON

1.Press the ENTER button to access the menu

2.Use the Up or Down arrow key to view the messages.

3.Press the ENTER button to select the message to be displayed.

4.3.15CUSTOM TEXT

This menu permits the user to set up a custom text message with a maximum length of 16 characters. The message may use any of the following characters or a blank space:

ABCDEFGHIJKLMNOPQURSTUVWXYZ#%*-0123456789

This custom text can be designated as the custom alarm text in the “CUSTOM ALARMS” menu (see CUSTOM ALARMS above). To define the message:

1.Press the ENTER button to access the menu.

2.Use the Up or Down arrow key to change the character with the pointer below it.

3.Press the ENTER button to go to the next character.

4.Repeat the steps for all characters in the message (maximum of 16 characters).

5.Press the ENTER button to accept new custom text.

4.3.16DIAGNOSTICS

This allows the user to perform checks on inputs, outputs, and conduct a test of the Liebert XDP con- trol board from the wall box.

Entering the “TEST OUTPUTS” will interrupt system operation. Selecting “TEST INPUTS” or “TEST MICRO” will not interrupt system operation. Pressing ENTER and selecting “TEST OUTPUTS” will permit the user to toggle the following outputs On and Off:

PUMP 1—On/Off PUMP 2—On/Off

CTR VALVE XX.Xma—OPEN/CLOSE (control valve and 4-20mA feedback signal) GREEN LAMP—On/Off

RED LAMP—On/Off COMMON ALARM—On/Off

Pressing ENTER and selecting “TEST INPUTS” will permit the user to read the following inputs:

INPUT POWER—On/Off CONDENSATION—On/Off (condensation detection) DIFF PRESSURE—On/Off (differential pressure switch) CUSTOMER ALARM—On/Off

Pressing ENTER and selecting “TEST MICRO” will permit the user to test the microcontroller and associated circuitry on the Liebert XDP control board.

27

Image 33
Contents Liebert XDP Example XDP160A General Safety GuidelinesFluorinated Greenhouse Gas Requirements-European Union Pumping Place holder Revision Unit Redundancy Level LiebertTable of Contents Specifications Alarm Descriptions and SolutionsFigures Page Equipment Inspection General Product InformationProduct Description Product/System DescriptionEquipment Handling Handling With SkidRemoval from Skid Liebert XDP strapped to piano jack Removing pallet boards for piano jack insertionSlide this runner away From the Liebert XDP Removing Piano JacksLiebert XDP dimensions Mechanical ConsiderationsPositioning the Liebert XDP Model Pipe Connection Point 50/60 Hz Unit piping outlet connection sizes, inches, OD CuElectrical Information High Voltage Connections Connecting High-Voltage CablesElectrical enclosure knockout locations for field wiring High voltage connections-50Hz Extra Low Voltage ELV ConnectionsField Connections-Optional for All Units Field Connections-All UnitsConnection Sizes European Union Fluorinated Greenhouse Gas RequirementsPiping Recommended Pipe SizeLiebert XDP Interconnection with Liebert XD Cooling Modules Piping Installation MethodBypass Flow Controller Bypass flow controllers for a Liebert XDP-based systemBypass flow controller arrangement Bypass flow controller details, dimensionsPiping Details-Shut-Off/Isolation Valves Piping Installation MethodPiping Mains Evacuation and Leak CheckChecklist for Proper Installation Checklist for Liebert XDP Startup Liebert XDP pump light indicator-208V and 400V unitsIndicator Lights Description Green Red System R-134a liquid level Filling the Pumped Circuit-R-134aSystem refrigerant charge for the supply and return mains Return Line Diameter 5/8Return Line Diameter Calculating refrigerant charge-example Calculating Refrigerant Charge-ExampleWorksheet to calculate refrigerant charge Total 293Microprocessor Control Feature OverviewDisplay User interface keypad functionsViewing or Changing Settings Feature OverviewControls Main MenuAlarm History Active AlarmsSetpoints MIN Temp SPRestart Time Delay Setup OperationDegrees Pump Start TDPump Wait TD Liebert XDP DIP switches and factory settingsPump OFF TD Lead PumpPassword Security-SETPT Password and Service Password Change Password-SETPT PasswordValve Time Alarm Enable Change Password-SERVICE PasswordAlarm Time Delay COM Alarm EnableCustom Alarms DiagnosticsCustom Text Alarm Descriptions and Solutions Alarm DescriptionsRed and Green Lamp Indicators Alter Alarm SettingsEnable or Disable Alarms System Shutdown Causes Troubleshooting the XDP TroubleshootingFluorinated Greenhouse Gas Requirements MaintenanceLiebert XDP160 specifications SpecificationsIti Ne tTi n That